Electrical Application Details for App #: Z115033
Premises: 629 WEST 135 STREET MANHATTAN BIN: 1059950     Block: 2002   Lot: 11
   
Application Completed and Certified

Filed: 629 W 135 ST Census Tract:   223.01 Health Area:  0900
MOTOR ROOM Admin Area:   Z - UPPER MANHATTAN Inspection Area:   B
NEW YORK, NY 10031 Community Board:   109
DOB Cross Street(s):   BROADWAY,    RIVERSIDE DRIVE
Status:   C - JOB IS SIGNED OFF 07/26/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/26/2007 1:21 PM
Application Entered:   11/26/2007 Job Start Date:   11/27/2007
Last Change:   07/26/2010 Job End Date:   08/27/2008
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     06/15/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011165 Licensee Name: JAMES KRUGER
Firm: 002557 Firm Name: VINTAGE ELEC. SERVICE INC
Firm Phone: 718-338-3910  Firm Address: 2812 HARWAY AVE BROOKLYN NY 11214 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: MAGAW MANAGEMENT LLC
Authorized Representative:  STEPHEN RUOCCO
Relationship To Owner:   EXPEDITOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  7 STORIES
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/01/2009
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  #968 REPLACE CONTROLLER, SHAFT AND CAR WIRING FOR ELEVATOR 1P9949

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z115033
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/29/2008 01/02/2009 FRI A (15) (3) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 10/29/2009 11/05/2009 CLC P (30) (0) Y
INSPECTION COMMENTS: NO ACCESS TO PIT - CONTRACTOR NO SHOW
 
(3) 11/19/2009 12/01/2009 DAH A R (30) (5) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(4) 06/15/2010 06/18/2010 CCH C R (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z115033
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
MACH.RM: E.M.T.TO MOTOR & TROUGH TO CONTROLLER
RSLV 12/29/2008 12/29/2008 11/19/2009
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
ELEVATOR PIT
RSLV 12/29/2008 12/29/2008 11/19/2009
 
003 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
MACH.PIT: DISCONNECT SWITCH
RSLV 12/29/2008 12/29/2008 11/19/2009
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
MACHINE ROOM: E.M.T.TO MOTOR AND TROUGH TO CONTROLLER
RSLV 11/19/2009 11/19/2009 06/15/2010
 
005 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
ELEV.RM: RACEWAY TO MOTOR NOT PROPERLY SUPPORTED
RSLV 11/19/2009 11/19/2009 06/15/2010
 
006 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
ELEV.RM: RACEWAY FROM D.S.NOT PROPERLY SUPPORTED
RSLV 11/19/2009 11/19/2009 06/15/2010
 
007 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
ELEV.RM: PNL FDR UNDER-SIZED #12 AWG
RSLV 11/19/2009 11/19/2009 06/15/2010
 
008 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
ELEV.RM: KO
RSLV 11/19/2009 11/19/2009 06/15/2010