BIS Menu  |  Elevators  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z113434
Premises: 326 WEST 71 STREET MANHATTAN BIN: 1030938     Block: 1182   Lot: 43
   
Application Completed and Certified

Filed: 326 W 71 ST Census Tract:   159 Health Area:  3900
GROUND FLOOR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   WEST END AVENUE,    RIVERSIDE BOULEVARD
Status:   C - JOB IS SIGNED OFF 05/30/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/31/2007 9:04 AM
Application Entered:   07/31/2007 Job Start Date:   08/03/2007
Last Change:   05/30/2012 Job End Date:   08/06/2007
Appointment Status:   
Last Inspection By:   BEST, J       On     04/11/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011119 Licensee Name: MIKHAIL ZARETSKY
Firm: 002490 Firm Name: ABLE ELEC'L SVC & MNT INC
Firm Phone: 917-270-6884  Firm Address: 2762 WEST 16TH STREET BROOKLYN NY 11224 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $298.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WILLIAM T FRIEDEWALD
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  30CKT,300A MAIN CKT BREAK
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  4# 500MCM,3 1/2" CONDUIT
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 20  25    17  20                
Total Units : 82 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 1
Existing Meters 2 + New Meters 0 - Removed Meters 0 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/31/2007 Notice: 1 - FIRST NOTICE 10/26/2011
Power Issued: 07/31/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z113434
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/14/2011 10/26/2011 CLC A E (30) (3) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 04/11/2012 04/17/2012 JSB C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z113434
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
GND FL: BEDROOMS OUTLETS,LIGHTS NOT A.F.C.I.PROTECTED.. - 210.12B
RSLV 10/14/2011 10/14/2011 04/11/2012
 
002 (999) OTHER
GND FL: PANEL LOCATED IN CLOTHES CLOSET..... - 240.24D
RSLV 10/14/2011 10/14/2011 04/11/2012
 
003 (999) OTHER
GND FL: SVC ENT RACEWAY IN THE HOLLOW FRAME OF THE BUILDING.... -230.43(E)
RSLV 10/14/2011 10/14/2011 04/11/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elevators  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back