BIS Menu  |  Marquee Query  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z111861
Premises: 177 WEST 88 STREET MANHATTAN BIN: 1032285     Block: 1219   Lot: 7
   
Application Completed and Certified

Filed: 177 W 88 ST Census Tract:   173 Health Area:  3220
BASEMENT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10024 Community Board:   107
Special Place Name:   COLUMBUS AND AMSTERDAM AVE
DOB Cross Street(s):   COLUMBUS AVENUE,    AMSTERDAM AVENUE
Status:   C - JOB IS SIGNED OFF 08/07/2008
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/15/2007 1:31 PM
Application Entered:   04/15/2007 Job Start Date:   04/20/2007
Last Change:   08/07/2008 Job End Date:   02/15/2008
Appointment Status:   
Last Inspection By:   BEST, J       On     07/01/2008      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011560 Licensee Name: YAM B GURUNG
Firm: 003226 Firm Name: J & Y ELECTRIC AND INTER*
Firm Phone: 212-831-5720  Firm Address: 1991 LEXINGTON AVENUE CO. INC. NEW YORK NY 10035 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $393.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBIN STATSKY
Owner Business Name: 9177638362
Authorized Representative:  ROBIN STATSKY
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  SINGLE PHASE100AMP SWITCH
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  2  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  4 #500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 2 - Removed Meters 1 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/15/2007 Notice: 1 - FIRST NOTICE 03/04/2008
Power Issued: 04/15/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  UPGRADE SERVICE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z111861
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/28/2008 03/04/2008 EBA A E (50) (2) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS - * SEE S/S COUNT*
 
(2) 07/01/2008 07/12/2008 JSB C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z111861
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: DOUBLE LUGGING ON MAIN NEUTRAL AND MAIN GROUND110.14.A
RSLV 02/28/2008 02/28/2008 07/01/2008
 
002 (999) OTHER
BSMT: GROUND ROD RACEWAY NOT CONTINIOUS250.92.A.3
RSLV 02/28/2008 02/28/2008 07/01/2008



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Marquee Query  |  Electrical Inspection Work Order  |  Back