BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z105976
Premises: 303 WEST 87 STREET MANHATTAN BIN: 1033973     Block: 1249   Lot: 28
   
Application Completed and Certified

Filed: 303 W 87 ST Census Tract:   175 Health Area:  3120
ENTIRE BLDG Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   WEST END AVENUE,    RIVERSIDE DRIVE
Status:   C - JOB IS SIGNED OFF 06/03/2009
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   09/14/2005 Job Start Date:   07/28/2005
Last Change:   06/03/2009 Job End Date:   07/31/2006
Appointment Status:   
Last Inspection By:   HINDS EUGENE       On     02/24/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010731 Licensee Name: JAY G HELFGOTT
Firm: 003349 Firm Name: JAY HELFGOTT ELEC. CORP.
Firm Phone: 718-753-0091  Firm Address: 220 ASHFORD STREET BROOKLYN NY 11207 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $479.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: MARC APPEZ
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 40  60    25  40     19           
Total Units : 184 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/14/2005 Notice: 1 - FIRST NOTICE 03/31/2008
Power Issued: 09/14/2005 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z105976
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/17/2008 03/31/2008 JSB A E (90) (3) Y
INSPECTION COMMENTS: SEE VIOLATION
 
(2) 02/24/2009 03/04/2009 EHD C R (20) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z105976
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
ALL SUB PNLS,NEUTRAL BONDED AFTER SVC SW 250.24 (A) 5
RSLV 03/17/2008 03/17/2008 02/24/2009
 
002 (999) OTHER
(A) BRANCH CKT WIRES NOT PROPERLY TERMINATED,NEUTRALS TERMINATED ONGRD BLOCK 250.4 (5)
RSLV 03/17/2008 03/17/2008 02/24/2009
 
003 (999) OTHER
(B) SEAL TIGHT NO GRD PROVIDED 250.118
RSLV 03/17/2008 03/17/2008 02/24/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.