Electrical Application Details for App #: Z100153
Premises: 126 CENTRAL PARK SOUTH MANHATTAN BIN: 1023758     Block: 1011   Lot: 45
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 128 CENTRAL PARK S Census Tract:   137 Health Area:  4700
NONE Admin Area:   Z - UPPER MANHATTAN Inspection Area:   F
NEW YORK, NY 10019 Community Board:   105
DOB Cross Street(s):   AVENUE OF THE AMERICAS,    CENTRAL PARK EXIT 7 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   04/22/2004 Job Start Date:   04/19/2004
Last Change:   08/22/2025 Job End Date:   07/19/2004
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     01/11/2018      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 009860 Licensee Name: JOSEPH TODARO
Firm: 002632 Firm Name: TNT ELECTRIC CO., INC.
Firm Phone: 347-763-2342  Firm Address: 41 BOX STREET, STE 301 BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
2 - TEMPORARY CONSTRUCTION
6 - GENERAL WIRING
Total Fee:  $117.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: MICHEAL HERMAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 32  40    17  32                
Total Units : 121 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 01/17/2018
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z100153
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/11/2018 01/17/2018 TUR V (50) (8)
INSPECTION COMMENTS: OBJECTIONS ISSUED, MUST CORRECT ISSUES PRIOR TO INSPECTION MEDICAL OFFICES AND OPERATING ROOM (OPERATING ROOM WIRING MUST BE MEDICAL GRADE AND GASES STORED IN SAME ROOM )

OBJECTION FOR APPLICATION #: Z100153
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
(FLOOR: 001)400.8 FLEXIBLE CORD THRU WALL FOR WIRING OF WATER COOLER
OPEN 01/11/2018 01/11/2018
 
002 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(FLOOR: 001)110.2 IN OPERATING ROOM HOSPITAL GRADE DEVICES NOT IN USE
OPEN 01/11/2018 01/11/2018
 
003 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 001)110.2 MEDICAL GRADE WIRING NOT IN USE IN OPERATING ROOM , AND ALSOTHIS ROOM HAAS OPERATING GASES SEE THE APPROPRIATE CODES AND FOLLOWINSTALLATION AND METHODS ALLOWED
OPEN 01/11/2018 01/11/2018
 
004 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(FLOOR: 001) 250.146 OUTLETS NOT GROUNDED PROPERLY THRU OUT
OPEN 01/11/2018 01/11/2018
 
005 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 001) 210.8 GFCI NOT PROVIDED IN ALL AREAS REQUIRED
OPEN 01/11/2018 01/11/2018
 
006 (999) OTHER
(FLOOR: 001)110.14, 240.21 THREE PANELS TAPPED OFF ONE SET OF FEEDERS IN MAINPANEL, UNDER ONE SET OF LUGS AND TAP OF TAP
OPEN 01/11/2018 01/11/2018
 
007 (999) OTHER
(FLOOR: 001)NOTE 1: THE DETAILS ON THE APPLICATION MUST BE CORRECTED FOR(LIGHTS, RECEPTACLES, SWITCHES, MOTORS, TRANSFORMERS , 3 PANELS ANDFEEDERS )
OPEN 01/11/2018 01/11/2018
 
008 (999) OTHER
(FLOOR: 001)110.26 CLEARANCES ABOUT PANELS IN CLOSET WITH COMBUSTIBLES
OPEN 01/11/2018 01/11/2018