| BUILDING OVERVIEW |
Are Feeders Being Installed? : |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 15) |
FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD (FLOOR: 001)400.8 FLEXIBLE CORD THRU WALL FOR WIRING OF WATER COOLER |
OPEN |
01/11/2018 |
01/11/2018 |
|
| |
| 002 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE (FLOOR: 001)110.2 IN OPERATING ROOM HOSPITAL GRADE DEVICES NOT IN USE |
OPEN |
01/11/2018 |
01/11/2018 |
|
| |
| 003 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 001)110.2 MEDICAL GRADE WIRING NOT IN USE IN OPERATING ROOM , AND ALSOTHIS ROOM HAAS OPERATING GASES SEE THE APPROPRIATE CODES AND FOLLOWINSTALLATION AND METHODS ALLOWED |
OPEN |
01/11/2018 |
01/11/2018 |
|
| |
| 004 |
(211) |
RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED (FLOOR: 001) 250.146 OUTLETS NOT GROUNDED PROPERLY THRU OUT |
OPEN |
01/11/2018 |
01/11/2018 |
|
| |
| 005 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 001) 210.8 GFCI NOT PROVIDED IN ALL AREAS REQUIRED |
OPEN |
01/11/2018 |
01/11/2018 |
|
| |
| 006 |
(999) |
OTHER (FLOOR: 001)110.14, 240.21 THREE PANELS TAPPED OFF ONE SET OF FEEDERS IN MAINPANEL, UNDER ONE SET OF LUGS AND TAP OF TAP |
OPEN |
01/11/2018 |
01/11/2018 |
|
| |
| 007 |
(999) |
OTHER (FLOOR: 001)NOTE 1: THE DETAILS ON THE APPLICATION MUST BE CORRECTED FOR(LIGHTS, RECEPTACLES, SWITCHES, MOTORS, TRANSFORMERS , 3 PANELS ANDFEEDERS ) |
OPEN |
01/11/2018 |
01/11/2018 |
|
| |
| 008 |
(999) |
OTHER (FLOOR: 001)110.26 CLEARANCES ABOUT PANELS IN CLOSET WITH COMBUSTIBLES |
OPEN |
01/11/2018 |
01/11/2018 |
|