Electrical Application Details for App #: Z098503
Premises: 263 WEST 139 STREET MANHATTAN BIN: 1060348     Block: 2025   Lot: 3
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 263 W 139 ST Census Tract:   230 Health Area:  1000
BSMT,1,2,3,4 Admin Area:   Z - UPPER MANHATTAN Inspection Area:   B
NEW YORK, NY 10030 Community Board:   110
Related Job Number:    103571528
DOB Cross Street(s):   PEDESTRIAN PATH,    FREDERICK DOUGLASS BOULEVARD
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   11/26/2003 Job Start Date:   10/25/2003
Last Change:   08/22/2025 Job End Date:   06/25/2004
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   JOFFRE PENA       On     08/08/2023      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011873 Licensee Name: NIKOLAOS HALKIAS
Firm: 003478 Firm Name: TOPLINE ELECTRIC CORP
Firm Phone: 718-358-8494  Firm Address: 20-39 128TH STREET COLLEGE POINT NY 11356 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $203.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: LAURA J LORIO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  4  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 90  70    25  90                
Total Units : 275 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 11/26/2003 Notice: 1 - FIRST NOTICE 08/09/2023
Power Issued: 11/26/2003 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z098503
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/08/2023 08/09/2023 JRP V (53) (4)
INSPECTION COMMENTS: HOME OWNER LOCKED HER SELF OUT. SERVICE INSPECTED ONLY. INSPECTION INCOMPLETE

OBJECTION FOR APPLICATION #: Z098503
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) COMMON AREAS NOT FROM PLP METER 210.25
OPEN 08/08/2023 08/08/2023
 
002 (999) OTHER
(ALL FLOORS)CONTRACTOR NEED TO FILE NEW APP TO ADD 1-200 AMP SERVICE SWITCH2-100 AMP SERVICE SWITCH FOR TOTAL OF THREE. 1-3/0 AWG SERVICECONDUCTORS , 3 DISCONNECT SWITCHES , 4-3 AWG FEEDER CONDUCTORS,TOTAL DEVICES ,TOTAL METERS
OPEN 08/08/2023 08/08/2023
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) MISSING GEC 250.64, 250.66
OPEN 08/08/2023 08/08/2023
 
004 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) NO MAIN BONDING JUMPER FOR ALL SERVICE SWITCHES 250.28
OPEN 08/08/2023 08/08/2023