Electrical Application Details for App #: Z096169
Premises: 351 COLUMBUS AVENUE MANHATTAN BIN: 1028823     Block: 1129   Lot: 64
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 66 W 77 ST Census Tract:   161 Health Area:  3500
BSMT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   CENTRAL PARK ENTRANCE W 77 ST,    COLUMBUS AVENUE
Status:   C - JOB IS SIGNED OFF 10/31/2016
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   06/04/2003 Job Start Date:   06/02/2003
Last Change:   10/31/2016 Job End Date:   12/31/2003
Appointment Status:   
Last Inspection By:   URIM SYLA       On     10/28/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011750 Licensee Name: MICHAEL MINIERO
Firm: 004273 Firm Name: ISTRA ELEC'L CONTRS CORP
Firm Phone: 718-740-8180  Firm Address: 69-24 49TH AVENUE STE 211 WOODSIDE NY 11377 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
011750 MINIERO, MICHAEL 003342 EMPIRE LIBERTY ELEC. CORP
011750 MINIERO, MICHAEL 003266 ISTRA ELEC'L CONTR'S CORP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
9 - OTHER
Total Fee:  $90.00
Other Work:   DC RECTIFIER FOR CON ED
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   X
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: FANNY GRUNBERG
Owner Business Name: FANNY GRUNBERG & ASSOC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/04/2003 Notice: C - CALL TO OFFICE 09/19/2016
Power Issued: 06/04/2003 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z096169
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/12/2012 05/29/2012 GYM A E (45) (5) Y
INSPECTION COMMENTS: *CONTRACTOR NO SHOW* SEE VIOLATION DETAILS
 
(2) 07/26/2012 08/10/2012 CJH N (20) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 09/16/2016 09/19/2016 CBK J X (30) (0) Y
INSPECTION COMMENTS: OBJECTION NOT REMOVED.
 
(4) 10/11/2016 10/17/2016 UMS N (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW , NO ANSWER
 
(5) 10/28/2016 10/31/2016 UMS C R (45) (0)
INSPECTION COMMENTS: OBJECTIONS CLEARED

OBJECTION FOR APPLICATION #: Z096169
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)BSMT: 100 AMP PANEL 100 AMP DISC SW NEUTRAL BAR BONDED AFTER S.SART.250.24
RSLV 05/12/2012 05/12/2012 10/28/2016
 
002 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ALL FLOORS) BSMT: E.M.T.TUBING FOR FEEDERS
RSLV 05/12/2012 05/12/2012 10/28/2016
 
003 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
(ALL FLOORS) BSMT: GREEN WIRING #12 AWG USED AS PHASE
RSLV 05/12/2012 05/12/2012 10/28/2016
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS)BSMT: EMPIRE RECTIFIED 15 KW 240VAC 62 AMPS INPUT 208 VAC 3 PHASE42 AMPS NOT GROUNDED
RSLV 05/12/2012 05/12/2012 10/28/2016
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) A) GREENFIELD NOT GROUNDED EMPIRE RECTIFIED
RSLV 05/12/2012 05/12/2012 10/28/2016