BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z057922
Premises: 503 COLUMBUS AVENUE MANHATTAN BIN: 1085066     Block: 1198   Lot: 1
   
Application Completed and Certified

Filed: 503 COLUMBUS AV Census Tract:   169 Health Area:  3500
STREET Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   WEST 84 STREET,    WEST 85 STREET
Status:   C - JOB IS SIGNED OFF 09/22/1999
Request Type:   C - COMPLAINT eFiled:   NO
Application Entered:   07/13/1994 Job Start Date:   07/19/1999
Last Change:   08/19/1999 Job End Date:   10/19/1999
Appointment Status:   
Last Inspection By:   GLAUBERZON, V       On     08/16/1999      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009615 Licensee Name: ROBERT COVELLO
Firm: 001205 Firm Name: ROBERT S. COVELLO
Firm Phone: 718-786-7390  Firm Address: 51-20 35TH STREET L.I.C. NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $10.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: J&D OPERATIONS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                     
Total Units : 6 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: R - OBJECTION(S) RESOL
Power Requested: Notice:  10/17/1994
Power Issued: Response: F - FILED TO REMOVE OBJECTION 07/29/1999

Follow-Up: X - FILED APPL,NOW CLOSED 07/29/1999
Contractor's Comments:  OUTSIDE LIGHTING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z057922
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/01/1994 08/11/1994 VG1 W (30) (4)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(4) 08/16/1999 08/19/1999 VG1 C R (40) (0) Y
INSPECTION COMMENTS: No Inspection Comments For This Application




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order