BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z047721
Premises: 351 COLUMBUS AVENUE MANHATTAN BIN: 1028823     Block: 1129   Lot: 64
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 351 COLUMBUS AV Census Tract:   161 Health Area:  3500
2396 NONE Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   WEST 76 STREET,    WEST 77 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   07/15/1992 Job Start Date:   09/14/1992
Last Change:   08/22/2025 Job End Date:   09/22/1992
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     07/26/2012      
Field Disp:   N - NO ACCESS
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  R - REMOVED

License #: 009756 Licensee Name: M HALPERN
Firm: 000951 Firm Name: MARTY ALLEN ELEC'L CO.,IN
Firm Phone: 212-254-9600  Firm Address: 108 EAST 16TH STREET NEW YORK NY 10003 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $33.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: FANNY&ARIEL GRUNGERG
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: R - REQUESTED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 09/24/1992 Notice: 1 - FIRST NOTICE 02/16/1993
Power Issued: 09/24/1992 Response: F - FILED TO REMOVE OBJECTION 09/24/1992

Follow-Up: F - FILED TO REMOVE OBJECTION 09/24/1992
Wires Comments: ALL WORK IN BSMT REPAIRG SERV AND BOX
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z047721
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/07/1992 07/15/1992 JBF W (15) (5)
INSPECTION COMMENTS: N/A
 
(3) 02/09/1993 02/16/1993 AG1 V R G (40) (6)
INSPECTION COMMENTS: *_COLUMBUS DOUBLE LUG
 
(4) 07/26/2012 08/10/2012 CJH N (15) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO LONGER IN BUSINESS ALMAN ELECTRIC BOUGH MARTY ALLEN ELECTRIC COMPANY PHONE NUMBER




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back