| BUILDING OVERVIEW |
Are Feeders Being Installed? : |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| SUB FEEDERS (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
7 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
7 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
1 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (ALL FLOORS) THROUGHOUT SER ENT TO END LINE SER SW ENCL, |
RSLV |
11/21/1989 |
11/21/1989 |
07/30/2019 |
| |
| 002 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (ALL FLOORS)GRD NOT MECHAN ICLY CONNECTED BROKEN ARMORED CABLE TO P IPE CLAMP, |
RSLV |
11/21/1989 |
11/21/1989 |
07/30/2019 |
| |
| 003 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ALL FLOORS) MAIN SER ENT NEUT BAR NOT BONDED TO SER SW ENCLOSURE |
RSLV |
11/21/1989 |
11/21/1989 |
07/30/2019 |
| |
| 004 |
( 48) |
TEMPORARY OPEN WIRING INSTALLED LESS THAN 7'6 (ALL FLOORS) THROUGHOUT BUILDING |
RSLV |
11/21/1989 |
11/21/1989 |
07/30/2019 |
| |
| 005 |
( 49) |
TEMPORARY OPEN WIRING INSTALLED IS NOT PROPERLY SUPPORTED (ALL FLOORS) THROUGHOUT BUILDING |
RSLV |
11/21/1989 |
11/21/1989 |
07/30/2019 |
| |
| 006 |
( 50) |
TEMPORARY OPEN WIRING IN CONTACT WITH PARTS OF THE BUILDING (ALL FLOORS) THROUGHOUT BUILDING |
RSLV |
11/21/1989 |
11/21/1989 |
07/30/2019 |
| |
| 007 |
( 51) |
TEMPORARY OPEN WIRING INSTALLED IS IMPROPERLY SPLICED (ALL FLOORS) THROUGHOUT BUILDING |
RSLV |
11/21/1989 |
11/21/1989 |
07/30/2019 |
| |
| 008 |
( 52) |
TEMPORARY OPEN WIRING FEEDS OTHER FLOORS (ALL FLOORS) THROUGHOUT BUILDING |
RSLV |
11/21/1989 |
11/21/1989 |
07/30/2019 |
| |
| 009 |
(999) |
OTHER (FLOOR: 003) PANEL IN CLOTHING CLOSET 27-3093 |
OPEN |
07/30/2019 |
07/30/2019 |
|
| |
| 010 |
(999) |
OTHER (FLOOR: 003) WHIRL POOL BATH TUB 27-3101, BUL # 133 |
OPEN |
07/30/2019 |
07/30/2019 |
|
| |
| 011 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ALL FLOORS) CHAIN HUNG FIXTURES |
OPEN |
07/30/2019 |
07/30/2019 |
|
| |
| 012 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (ALL FLOORS) PANELS |
OPEN |
07/30/2019 |
07/30/2019 |
|
| |
| 013 |
(999) |
OTHER (ALL FLOORS) PANELS DIRECTORS MISSING 27-3129 |
OPEN |
07/30/2019 |
07/30/2019 |
|
| |
| 014 |
(999) |
OTHER (ALL FLOORS) PAA REQUIRED 3 NEW PANELS, MORE LIGHTS. |
OPEN |
07/30/2019 |
07/30/2019 |
|
| |
| 015 |
(999) |
OTHER (ALL FLOORS) AC RECEPTACLES 27-3115 |
OPEN |
07/30/2019 |
07/30/2019 |
|
| |
| 016 |
(999) |
OTHER (ALL FLOORS) MULTI WIRE BRANCH CIRCUITS 27-3166 |
OPEN |
07/30/2019 |
07/30/2019 |
|
| |
| 017 |
(999) |
OTHER (ALL FLOORS) FIXTURES NOT APPROVED DAMP LOCATION 27-3137 |
OPEN |
07/30/2019 |
07/30/2019 |
|
| |
| 018 |
(999) |
OTHER (ALL FLOORS) SUB PANELS NEUTRAL BONDED 27-3110 |
OPEN |
07/30/2019 |
07/30/2019 |
|
| |
| 019 |
( 29) |
OUTLET BOXES ARE NOT COVERED (BASEMENT) BASEMENT. |
OPEN |
07/30/2019 |
07/30/2019 |
|
| |
| 020 |
(999) |
OTHER (BASEMENT) MAIN BREAKER NOT BOLT IN 27-3027 |
OPEN |
07/30/2019 |
07/30/2019 |
|
| |
| 021 |
(999) |
OTHER (BASEMENT) SERVICE SW. NEUTRAL NOT BONDED 27-3106 |
OPEN |
07/30/2019 |
07/30/2019 |
|