BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z026187
Premises: 319 WEST 108 STREET MANHATTAN BIN: 1057318     Block: 1893   Lot: 111
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 319 W 108 ST Census Tract:   195 Health Area:  2310
NONE Admin Area:   Z - UPPER MANHATTAN Inspection Area:   C
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   BROADWAY,    RIVERSIDE DRIVE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   05/02/1989 Job Start Date:   04/10/1989
Last Change:   08/22/2025 Job End Date:   04/29/1989
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     07/30/2019      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  B - CANCEL POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010359 Licensee Name: LEROY P MCCLARIN
Firm: 000844 Firm Name: L.P. DAVIS ELECTRIC CO.
Firm Phone: 212-926-8070  Firm Address: 57 MADISON STREET BROOKLYN NY 11238 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $245.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:   A - ADEQUATE WIRING PROGRAM
Advisory Board Approval:  
Owner / Occup: YVONNE STATFORD
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
SUB FEEDERS (EACH SET)  
A. Up to #2 CONDUCTOR  7  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  7  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 89  75  10  75                  
Total Units : 249 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

Access:   9AM TO 3PM Contact Phone:   662 5492

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 7 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: K - CANCELLED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 03/07/1994 Notice: 1 - FIRST NOTICE 07/31/2019
Power Issued: 05/02/1989 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z026187
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/21/1989 01/08/1990 MF1 V B (45) (8)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 03/02/1990 03/20/1990 RID Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(3) 04/10/1990 04/23/1990 RID N (30) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(4) 11/20/1990 11/29/1990 RID N (30) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(5) 03/02/1994 03/07/1994 RID H X B (30) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(6) 07/19/2019 07/20/2019 DNM N (15) (0) Y
INSPECTION COMMENTS: ELECTRICIAN DID NOT SHOW.
 
(7) 07/30/2019 07/31/2019 GYM V R (45) (13)
INSPECTION COMMENTS: SEE APP # Z012277

OBJECTION FOR APPLICATION #: Z026187
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(ALL FLOORS) THROUGHOUT SER ENT TO END LINE SER SW ENCL,
RSLV 11/21/1989 11/21/1989 07/30/2019
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(ALL FLOORS)GRD NOT MECHAN ICLY CONNECTED BROKEN ARMORED CABLE TO P IPE CLAMP,
RSLV 11/21/1989 11/21/1989 07/30/2019
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) MAIN SER ENT NEUT BAR NOT BONDED TO SER SW ENCLOSURE
RSLV 11/21/1989 11/21/1989 07/30/2019
 
004 ( 48) TEMPORARY OPEN WIRING INSTALLED LESS THAN 7'6
(ALL FLOORS) THROUGHOUT BUILDING
RSLV 11/21/1989 11/21/1989 07/30/2019
 
005 ( 49) TEMPORARY OPEN WIRING INSTALLED IS NOT PROPERLY SUPPORTED
(ALL FLOORS) THROUGHOUT BUILDING
RSLV 11/21/1989 11/21/1989 07/30/2019
 
006 ( 50) TEMPORARY OPEN WIRING IN CONTACT WITH PARTS OF THE BUILDING
(ALL FLOORS) THROUGHOUT BUILDING
RSLV 11/21/1989 11/21/1989 07/30/2019
 
007 ( 51) TEMPORARY OPEN WIRING INSTALLED IS IMPROPERLY SPLICED
(ALL FLOORS) THROUGHOUT BUILDING
RSLV 11/21/1989 11/21/1989 07/30/2019
 
008 ( 52) TEMPORARY OPEN WIRING FEEDS OTHER FLOORS
(ALL FLOORS) THROUGHOUT BUILDING
RSLV 11/21/1989 11/21/1989 07/30/2019
 
009 (999) OTHER
(FLOOR: 003) PANEL IN CLOTHING CLOSET 27-3093
OPEN 07/30/2019 07/30/2019
 
010 (999) OTHER
(FLOOR: 003) WHIRL POOL BATH TUB 27-3101, BUL # 133
OPEN 07/30/2019 07/30/2019
 
011 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) CHAIN HUNG FIXTURES
OPEN 07/30/2019 07/30/2019
 
012 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ALL FLOORS) PANELS
OPEN 07/30/2019 07/30/2019
 
013 (999) OTHER
(ALL FLOORS) PANELS DIRECTORS MISSING 27-3129
OPEN 07/30/2019 07/30/2019
 
014 (999) OTHER
(ALL FLOORS) PAA REQUIRED 3 NEW PANELS, MORE LIGHTS.
OPEN 07/30/2019 07/30/2019
 
015 (999) OTHER
(ALL FLOORS) AC RECEPTACLES 27-3115
OPEN 07/30/2019 07/30/2019
 
016 (999) OTHER
(ALL FLOORS) MULTI WIRE BRANCH CIRCUITS 27-3166
OPEN 07/30/2019 07/30/2019
 
017 (999) OTHER
(ALL FLOORS) FIXTURES NOT APPROVED DAMP LOCATION 27-3137
OPEN 07/30/2019 07/30/2019
 
018 (999) OTHER
(ALL FLOORS) SUB PANELS NEUTRAL BONDED 27-3110
OPEN 07/30/2019 07/30/2019
 
019 ( 29) OUTLET BOXES ARE NOT COVERED
(BASEMENT) BASEMENT.
OPEN 07/30/2019 07/30/2019
 
020 (999) OTHER
(BASEMENT) MAIN BREAKER NOT BOLT IN 27-3027
OPEN 07/30/2019 07/30/2019
 
021 (999) OTHER
(BASEMENT) SERVICE SW. NEUTRAL NOT BONDED 27-3106
OPEN 07/30/2019 07/30/2019