BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z024995
Premises: 501 COLUMBUS AVENUE MANHATTAN BIN: 1031291     Block: 1198   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 501 COLUMBUS AV Census Tract:   169 Health Area:  3500
NONE Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10024 Community Board:   107
DOB Cross Street(s):   WEST 84 STREET,    WEST 85 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   03/01/1989 Job Start Date:   04/29/1989
Last Change:   08/22/2025 Job End Date:   04/29/1989
Appointment Status:   
Last Inspection By:   ADMINISTRATION       On     11/05/1999      
Field Disp:   W - ISSUE OBJECTION TO OWNER
Energize Recommendation:  
Objection Disposition:  

License #: 009909 Licensee Name: J BEMUS
Firm: 000217 Firm Name: BEMUS ELEC'L CONTRS.
Firm Phone: 718-217-4100  Firm Address: 202-16 99TH AVENUE HOLLIS NY 11423 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $5.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   DELI
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: PARISINAN DELICATESSEN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                     
Total Units : 10 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

Access:   DAILY 8 TO 4PM Contact Phone:   718 217-4100

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice:  04/24/1989
Power Issued: Response: F - FILED TO REMOVE OBJECTION 05/05/1989

Follow-Up: F - FILED TO REMOVE OBJECTION 05/05/1989
Wires Comments: REMOVE VIO AS LISTED
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z024995
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/09/1989 03/01/1989 FCO W (15) (3)
INSPECTION COMMENTS: No Inspection Comments For This Application




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order