| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
2 |
30AMP |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
5 |
1600/2000/800/600/200 |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
12 |
8 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
10 |
1/0 3/0 |
| D. Over 250 MCM |
24 |
350/500/400/600 |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
4 |
200 |
| D. 3 Phase Over 225 AMPS |
2 |
600/1600 |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (ALL FLOORS) GROUNDING RACEWAY NOT CONTINUOUS 250.64 |
RSLV |
09/13/2018 |
09/13/2018 |
03/16/2019 |
| |
| 002 |
(999) |
OTHER (GROUND FLOOR) 200 AMP SERVICE SW. NEUTRAL NOT BONDED 250.28 |
RSLV |
09/13/2018 |
09/13/2018 |
03/16/2019 |
| |
| 003 |
(999) |
OTHER (GROUND FLOOR) SERVICE ENTRANCE CONDUIT NOT BONDED 250.92 |
RSLV |
09/13/2018 |
09/13/2018 |
03/16/2019 |
| |
| 004 |
(999) |
OTHER (GROUND FLOOR) ALL BONDING JUMPERS UNDER SIZE 250.66 |
RSLV |
09/13/2018 |
09/13/2018 |
03/16/2019 |
| |
| 005 |
(999) |
OTHER (GROUND FLOOR) RESIDENTIAL DIST. BOARD IS NOT AS PER DRAWING 110.2 |
RSLV |
09/13/2018 |
09/13/2018 |
03/16/2019 |
| |
| 006 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (ROOF) ROOF |
RSLV |
09/13/2018 |
09/13/2018 |
03/16/2019 |
| |
| 007 |
(999) |
OTHER (ROOF) NO GROUNDING ELECTRODE CONDUCTOR FOR GENERATOR 250.20 |
RSLV |
09/13/2018 |
09/13/2018 |
03/16/2019 |
| |
| 008 |
(999) |
OTHER (GROUND FLOOR) GROUNDING RACEWAY NOT CONTINUOUS 250.64 |
RSLV |
03/16/2019 |
03/16/2019 |
04/05/2019 |
| |
| 009 |
(999) |
OTHER (GROUND FLOOR) SERVICE ENTRANCE CONDUITS BONDING UNDER SIZE 250.66 |
RSLV |
03/16/2019 |
03/16/2019 |
04/05/2019 |
| |
| 010 |
(999) |
OTHER (GROUND FLOOR)PARALLEL CONDUCTORS IS NOT TERMINATED IN THE SAME MANNER 310.4 |
RSLV |
03/16/2019 |
03/16/2019 |
04/05/2019 |