BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y185269
Premises: 425 EAST 154 STREET BRONX BIN: 2001389     Block: 2376   Lot: 30
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 425 E 154TH ST Census Tract:   67 Health Area:  3900
BASEMENT TO ROOF Admin Area:   Y - BRONX Inspection Area:   B
BRONX, NY 10455 Community Board:   201
DOB Cross Street(s):   MELROSE AVENUE,    ELTON AVENUE
Status:   C - JOB IS SIGNED OFF 01/17/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/09/2017 7:40 AM
Application Entered:   11/09/2017 Job Start Date:   11/09/2017
Last Change:   01/17/2019 Job End Date:   11/08/2018
Appointment Status:   
Last Inspection By:   RICHARD REED       On     11/30/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012486 Licensee Name: ANTHONY QUINONES
Firm: 004300 Firm Name: QUEUE ELEC'L CONTRS, INC
Firm Phone: 718-353-7700  Firm Address: 94-02 LINDEN BLVD 1ST FLOOR OZONE PARK NY 11417 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $935.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SASHA CATUS
Owner Business Name: 425 EAST 154TH STREET LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  8  40AMP
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  200AMP
D. Over 250 MCM  2  2-350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  8  100AMP
C. 3 Phase Up to 225 AMPS  1  200AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    10    10  10     
001    34  36  34         
002    34  36  34         
003    34  36  34         
004    34  36  34         
ROF             
Buildings Total 148  149  16  27  148     20         
Total Units : 511 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 8 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 9 - Removed Meters 0 = Total Meters 9

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/09/2017 Notice: 1 - FIRST NOTICE 11/13/2018
Power Issued: 11/09/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GUT REHAB & BUILDING EXTENSION

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y185269
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/13/2018 11/13/2018 JRP V (90) (5)
INSPECTION COMMENTS: FAIL
 
(2) 11/30/2018 11/30/2018 RDY C R (34) (0)
INSPECTION COMMENTS: INSPECTION PASSED.

OBJECTION FOR APPLICATION #: Y185269
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)ALL BREAKERS IN ALL PANELS NOT LISTED FOR PANELS 110.3(B)
RSLV 11/13/2018 11/13/2018 11/30/2018
 
002 (999) OTHER
(ALL FLOORS) AL PANELS NO DIRECTORY 408.4
RSLV 11/13/2018 11/13/2018 11/30/2018
 
003 (999) OTHER
(BASEMENT) NO MAIN BONDING JUMPER FOR SERVICE SWITCH 250.28
RSLV 11/13/2018 11/13/2018 11/30/2018
 
004 (999) OTHER
(BASEMENT) FLAMMABLE MATERIAL IN ELECTRICAL ROOM
RSLV 11/13/2018 11/13/2018 11/30/2018
 
005 (999) OTHER
(BASEMENT) NO INTERSYSTEM BONDING 250.94, 800.100(B)
RSLV 11/13/2018 11/13/2018 11/30/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order