BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y183525
Premises: 2368 UNIVERSITY AVENUE BRONX BIN: 2014614     Block: 3212   Lot: 63
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 2374 DR.MARTIN LUTHER KING JR.BLVD. Census Tract:   253 Health Area:  1520
BASEMENT Admin Area:   Y - BRONX Inspection Area:   F
BRONX, NY 10468 Community Board:   207
DOB Cross Street(s):   WEST 183 STREET,    DEVOE PARK PATH
Status:   C - JOB IS SIGNED OFF 01/24/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/24/2017 11:12 AM
Application Entered:   07/24/2017 Job Start Date:   07/24/2017
Last Change:   01/24/2020 Job End Date:   12/31/2017
Appointment Status:   
Last Inspection By:   RICHARD REED       On     01/24/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012748 Licensee Name: EDWARD C CUFF
Firm: 004588 Firm Name: E.C. ELECL CONTRACTOR INC
Firm Phone: 718-231-0574  Firm Address: 27 EAST 233RD STREET BRONX NY 10470 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $115.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RONALD MOORE
Owner Business Name: T-MOBILE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMPS
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1 SET 3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/24/2017 Notice: 1 - FIRST NOTICE 11/20/2019
Power Issued: 07/24/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y183525
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/23/2018 04/23/2018 JRP N (20) (0) Y
INSPECTION COMMENTS: SPOKE TO CONTRACTOR WILL RESCHEDULE
 
(2) 11/20/2019 11/20/2019 GIG V (47) (4)
INSPECTION COMMENTS: INSPECTION FAILED
 
(3) 01/24/2020 01/24/2020 RDY C R (39) (0)
INSPECTION COMMENTS: INSPECTION PASSED. CONTRACTOR HAD 4 OBJECTIONS HE REMOVED ALL 4 OBJECTIONS. SERVICE SWITCH WAS MOVED AND ALL SERVICE GROUNDING IS GOOD, 2"EMT IS NOW SUPPORTED. GROUND ROD INSTALLED. JOB IS GOOD.

OBJECTION FOR APPLICATION #: Y183525
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (133) NO GROUND ROD: BASEMENT OR OUTSIDE
(BASEMENT) NO SUPPLEMENTAL GROUND
RSLV 11/20/2019 11/20/2019 01/24/2020
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT) 200 AMP SERVICE SWITCH NOT PROPERLY GROUNDED/BONDED
RSLV 11/20/2019 11/20/2019 01/24/2020
 
003 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT) EMT NOT INDEPENDENTLY SUPPORTED
RSLV 11/20/2019 11/20/2019 01/24/2020
 
004 (999) OTHER
(BASEMENT) NO CLEARANCE INFRONT OF SERVICE SWITCH 110.26
RSLV 11/20/2019 11/20/2019 01/24/2020



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.