BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y183362
Premises: 3251 WHITE PLAINS ROAD BRONX BIN: 2056223     Block: 4595   Lot: 26
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 686 ROSEWOOD ST Census Tract:   374 Health Area:  0810
BASEMENT, 1, 2,3,4,5 FLOORS Admin Area:   Y - BRONX Inspection Area:   G
BRONX, NY 10467 Community Board:   212
DOB Cross Street(s):   OLINVILLE AVENUE,    WHITE PLAINS ROAD
Status:   C - JOB IS SIGNED OFF 06/15/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/12/2017 5:56 PM
Application Entered:   07/12/2017 Job Start Date:   07/14/2017
Last Change:   06/15/2018 Job End Date:   12/14/2017
Appointment Status:   
Last Inspection By:   GIUSEPPE IMBURGIA       On     05/29/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011063 Licensee Name: MELVIN A BRANDL
Firm: 000219 Firm Name: BRANDL ELECTRIC INC.
Firm Phone: 718-327-5677  Firm Address: 71-34 MAIN STREET FLUSHING NY 11367 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
9 - OTHER
Total Fee:  $944.00
Other Work:   ADEQUATE WIRING
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: STEVEN FINKELSTEIN
Owner Business Name: FINKELSTEIN TIMBERGER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  29  #6/3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  29  100 AMP MAIN LUG
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND  1-5    15  11                 
001  1A-1D    12                 
002  2A-2D    12                 
003  3A-3D    12                 
004  4A-4D    12                 
005  5A-5D    12                 
006  6A-6D    12                 
Buildings Total   87  59                    
Total Units : 146 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 30 #4-Wire 0 #10-Wire 0
Existing Meters 30 + New Meters 30 - Removed Meters 0 = Total Meters 60

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/12/2017 Notice: C - CALL TO OFFICE 04/13/2018
Power Issued: 07/12/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ADEQUATE WIRING PROGRAM

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y183362
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/16/2018 02/20/2018 GIG J (60) (0) Y
INSPECTION COMMENTS: I DID A WALK THROUGH WITH ELECTRICAL CONTRACTORS CONTRACTORS REP. DID NOT KNOW SCOPE OF WORK
 
(2) 03/15/2018 03/15/2018 JRP V (55) (1)
INSPECTION COMMENTS: FAIL
 
(3) 03/14/2018 03/16/2018 JRP V X (5) (2)
INSPECTION COMMENTS: FAIL
 
(4) 04/13/2018 04/13/2018 JRP J X (45) (0) Y
INSPECTION COMMENTS: ACCORDING TO LOAD CALCULATION CONTRACTOR WILL UPGRADE ELECTRICAL SYSTEM. MULTI BRANCH CIRCUIT OBJECTION REMOVED.
 
(5) 05/29/2018 05/29/2018 GIG C R (25) (0)
INSPECTION COMMENTS: INSPECTION PASSED

OBJECTION FOR APPLICATION #: Y183362
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)DOUBLE POLE BREAKER FOR KITCHEN CIRCUITS IN ALL APARTMENTS NOTLISTED FOR PANEL 110.3(B)
RSLV 03/15/2018 03/15/2018 05/29/2018
 
002 (999) OTHER
(ALL FLOORS)DOUBLE POLE BREAKER FOR KITCHEN CIRCUITS IN ALL APARTMENTS NOTLISTED FOR PANEL 110.3(B)
RSLV 03/14/2018 03/14/2018 05/29/2018
 
003 (999) OTHER
(BASEMENT)CONTRACTOR NEED LOAD CALCULATION LETTER FOR SINGLE PHASE SERVICESWITCH (29 ( APARTMENTS+PLP PANEL) 220.40
RSLV 03/14/2018 03/14/2018 05/29/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back