BIS Menu  |  Property Profile  |  DOB Violations  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y182551
Premises: 710 HUNTS POINT AVENUE BRONX BIN: 2006562     Block: 2763   Lot: 248
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 710 HUNTS POINT AV Census Tract:   117 Health Area:  4300
1 FL Admin Area:   Y - BRONX Inspection Area:   J
BRONX, NY 10474 Community Board:   202
DOB Cross Street(s):   SPOFFORD AVENUE,    FAILE STREET
Status:   C - JOB IS SIGNED OFF 04/16/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/19/2017 4:31 PM
Application Entered:   05/19/2017 Job Start Date:   05/19/2017
Last Change:   04/16/2019 Job End Date:   05/18/2018
Appointment Status:   
Last Inspection By:   RICHARD REED       On     04/05/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011878 Licensee Name: EDGAR LEVENSTEIN
Firm: 003500 Firm Name: CONTACT PLUS ELEC'L CORP
Firm Phone: 718-254-0291  Firm Address: 2922 SHELL ROAD BROOKLYN NY 11224 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BEN GOLD
Owner Business Name: MP MANAGEMENT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  7 STOPS
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 01/29/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y182551
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/26/2017 07/27/2017 JRP V (40) (5)
INSPECTION COMMENTS: FAIL
 
(2) 11/19/2018 11/19/2018 JRP J Y (40) (0)
INSPECTION COMMENTS: SOME OBJECTIONS REMOVED.
 
(3) 11/29/2018 11/29/2018 JRP H X (30) (0) Y
INSPECTION COMMENTS: NO PROGRESS ON JOB
 
(4) 01/29/2019 01/29/2019 EVG V X (26) (2)
INSPECTION COMMENTS: FAIL
 
(5) 04/05/2019 04/05/2019 RDY C R (46) (0)
INSPECTION COMMENTS: INSPECTION PASSED . NYC ID 2P992 . ELEVATOR HAS 7 STOPS. THERE WERE 3 OBJECTIONS , CONTRACTOR HAS REMOVED THE 3 OBJECTIONS

OBJECTION FOR APPLICATION #: Y182551
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT)FEEDERS GOING BACK TO THE ELECTRICAL ARE ROOM GOING TROUGH PANELS,METER AND TROFF BEFORE ENDS IN DISCONNECT 110.3
RSLV 07/26/2017 07/26/2017 11/19/2018
 
002 (999) OTHER
(BASEMENT) EMT NO SUPPORT 358.30
RSLV 07/26/2017 07/26/2017 04/05/2019
 
003 (999) OTHER
(BASEMENT) USING A PLUMBER RUBBER COUPLING WITH EMT 110.3
RSLV 07/26/2017 07/26/2017 11/19/2018
 
004 (999) OTHER
(BASEMENT) ALL DISCONNECTS WITH DIFFERENT FUSES 240.3
RSLV 07/26/2017 07/26/2017 11/19/2018
 
005 (999) OTHER
(BASEMENT) GROUNDING WIRE NOT TERMINATED IN SPLICE BOX 250.8
RSLV 07/26/2017 07/26/2017 11/19/2018
 
006 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT)WIRES ARE NOT COLOR CODED IN ELEVATOR DISCONNECT GOING TO THECONTROLLER.
RSLV 01/29/2019 01/29/2019 04/05/2019
 
007 (999) OTHER
(BASEMENT) PIT GFCI AND WATER RECEPTACLE ARE ON THE SAME CIRCUIT.
RSLV 01/29/2019 01/29/2019 04/05/2019