Electrical Application Details for App #: Y181884
Premises: 925 HUNTS POINT AVENUE BRONX BIN: 2129345     Block: 2735   Lot: 20
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 925 HUNTS POINT AV Census Tract:   89 Health Area:  3700
STREET Admin Area:   Y - BRONX Inspection Area:   C
BRONX, NY 10459 Community Board:   202
DOB Cross Street(s):   BRUCKNER BOULEVARD,    EAST 163 STREET
Status:   C - JOB IS SIGNED OFF 10/24/2021
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/04/2017 11:18 AM
Application Entered:   04/04/2017 Job Start Date:   04/05/2017
Last Change:   10/24/2021 Job End Date:   04/02/2018
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     10/23/2021      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011168 Licensee Name: HAROLD J MCGUIRE
Firm: 002560 Firm Name: MCGUIRE ELECTRICAL CORP.
Firm Phone: 718-998-6089  Firm Address: 2094 EAST 68TH STREET BROOKLYN NY 11234 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $790.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   MCDONALDS
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: EDGAR RIZO
Owner Business Name: COLLEY GROUP
Authorized Representative:  HAROLD MCGUIRE
Relationship To Owner:   ELECTRICIAN


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  1-800A SWITCH
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  2-SETS 4WIRE 500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  6  4-225 A / 2-90A PANELS
D. 3 Phase Over 225 AMPS  1  1-800A COMBO
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/04/2017 Notice: 1 - FIRST NOTICE 08/17/2017
Power Issued: 04/04/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLING NEW METER AND PANELS FOR STORE, OFF OF EXISTING SERVICE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y181884
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/16/2017 08/17/2017 JRP V (60) (4)
INSPECTION COMMENTS: FAIL
 
(2) 10/23/2021 10/24/2021 GYM C R (30) (0)
INSPECTION COMMENTS: SEE APP # X00051541 COMPLETE.

OBJECTION FOR APPLICATION #: Y181884
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) MAIN DISCONNECT AND PANEL OVER FUSE 240.3, 310.16
RSLV 08/16/2017 08/16/2017 10/23/2021
 
002 (999) OTHER
(BASEMENT) MAIN FEEDERS IN FMC NOT SUPPORTED 348.30
RSLV 08/16/2017 08/16/2017 10/23/2021
 
003 (999) OTHER
(BASEMENT) SPLICE BOX FOR FEEDERS NOT BONDED 250.118
RSLV 08/16/2017 08/16/2017 10/23/2021
 
004 (999) OTHER
(BASEMENT)NEEDS FUSE COORDINATION BETWEEN SERVICE, SECOND AND THIRD SWITCH
RSLV 08/16/2017 08/16/2017 10/23/2021



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.