BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y180955
Premises: 925 HUNTS POINT AVENUE BRONX BIN: 2129345     Block: 2735   Lot: 20
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 925 HUNTS POINT AV Census Tract:   89 Health Area:  3700
FIRST FLOOR Admin Area:   Y - BRONX Inspection Area:   C
BRONX, NY 10459 Community Board:   202
DOB Cross Street(s):   BRUCKNER BOULEVARD,    EAST 163 STREET
Status:   C - JOB IS SIGNED OFF 10/24/2021
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/26/2017 11:31 AM
Application Entered:   01/26/2017 Job Start Date:   01/27/2017
Last Change:   10/24/2021 Job End Date:   01/16/2019
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     10/23/2021      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011168 Licensee Name: HAROLD J MCGUIRE
Firm: 002560 Firm Name: MCGUIRE ELECTRICAL CORP.
Firm Phone: 718-998-6089  Firm Address: 2094 EAST 68TH STREET BROOKLYN NY 11234 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $269.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   MCDONALDS
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: MCDONALDS
Authorized Representative:  HAROLD MCGUIRE
Relationship To Owner:   ELECTRICIAN


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1   4-#2
C. Over 1/0 to 250 MCM  1  4-#3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  1-100A COMBO--1-225ACOMBO
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    72  74    72         
Buildings Total 72  74    72              
Total Units : 226 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/17/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ELECTRIC WORK FOR MCDONALDS ONLY ELECTRIC SERVICE AND METER ARE EXISTING AND WERE INSTALLED BY BASE BUILDING CONTRACTOR

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y180955
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/16/2017 08/17/2017 JRP V (30) (3)
INSPECTION COMMENTS: FAIL
 
(2) 10/23/2021 10/24/2021 GYM C R (25) (0)
INSPECTION COMMENTS: COMPLETE.

OBJECTION FOR APPLICATION #: Y180955
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(GROUND FLOOR) TEMP LIGHT AND POWER NOT REMOVED NYC AMENDMENT 590.8
RSLV 08/16/2017 08/16/2017 10/23/2021
 
002 (999) OTHER
(GROUND FLOOR) NO GFCI IN KITCHEN AREA 210.8(B)
RSLV 08/16/2017 08/16/2017 10/23/2021
 
003 (999) OTHER
(GROUND FLOOR) USED OF LFNC IN FREEZERS NYC AMENDMENT 356.10
RSLV 08/16/2017 08/16/2017 10/23/2021



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.