BIS Menu  |  Bldg Info Search  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y180380
Premises: 1038 SOUTHERN BOULEVARD BRONX BIN: 2006018     Block: 2743   Lot: 11
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1038 SOUTHERN BLVD Census Tract:   119 Health Area:  2900
BASEMENT Admin Area:   Y - BRONX Inspection Area:   C
BRONX, NY 10459 Community Board:   202
DOB Cross Street(s):   ALDUS STREET,    WESTCHESTER AVENUE
Status:   C - JOB IS SIGNED OFF 02/08/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/08/2016 8:59 AM
Application Entered:   12/08/2016 Job Start Date:   12/10/2016
Last Change:   02/08/2017 Job End Date:   02/10/2017
Appointment Status:   
Last Inspection By:   JOFFRE PENA       On     12/21/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011363 Licensee Name: JACOB NAFTALY
Firm: 002781 Firm Name: JACOBS ELECTRIC CORP.
Firm Phone: 718-533-9355  Firm Address: 37-31 58TH STREET, STE A-11 WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
5 - FIRE DAMAGE
Total Fee:  $55.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 18 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BLVD LLC 1038 SOUTHREN
Owner Business Name: HOULIHAN PARNES
Authorized Representative:  NAFTALY JACOB
Relationship To Owner:   ELECTRICIAN


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  2/0
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 12/21/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RESTORE ELECTRIC TO BUILDING AFTER FIRE IN 1 APARTMENT FIXGROUND WIRE IN BASEMRNT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y180380
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/15/2016 12/15/2016 JRP V (45) (3)
INSPECTION COMMENTS: FAIL
 
(2) 12/20/2016 12/21/2016 JRV J X (15) (0) Y
INSPECTION COMMENTS: HEAVY DUTY SIDE WALK SHED PRESENT AT TIME OF INSPECTION.
 
(3) 12/21/2016 12/22/2016 JRP C R (35) (0)
INSPECTION COMMENTS: NO OBJECTIONS IN COMPUTER BUT THERE IS ON BIS. OBJECTIONS REMOVED , JOB COMPLETE

OBJECTION FOR APPLICATION #: Y180380
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) NO GEC FROM BOTH SERVICE SWITCH DISCONNECTS 250.66
RSLV 12/15/2016 12/15/2016 12/21/2016
 
002 (999) OTHER
(GROUND FLOOR) NO GROUND ROD 250.52(A)(5)
RSLV 12/15/2016 12/15/2016 12/21/2016
 
003 (999) OTHER
(GROUND FLOOR)MAIN SERVICE SWITCH DISCONNECTS NOT READILY ACCESSIBLE230.70(A)(1)
RSLV 12/15/2016 12/15/2016 12/21/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Bldg Info Search  |  Electrical Inspection Work Order  |  Back