BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y180361
Premises: 499 EAST 188 STREET BRONX BIN: 2127594     Block: 3058   Lot: 41
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 499 E 188TH ST Census Tract:   387 Health Area:  1000
BASEMENT Admin Area:   Y - BRONX Inspection Area:   I
BRONX, NY 10458 Community Board:   206
Related Job Number:    201066489
DOB Cross Street(s):   WASHINGTON AVENUE,    BATHGATE AVENUE
Status:   C - JOB IS SIGNED OFF 01/04/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/06/2016 7:38 PM
Application Entered:   12/06/2016 Job Start Date:   12/07/2016
Last Change:   01/04/2017 Job End Date:   12/13/2016
Appointment Status:   
Last Inspection By:   DIMAGGIO, PHILLIP       On     12/29/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010379 Licensee Name: ANTE KRSLOVIC
Firm: 000875 Firm Name: LINA ELECTRIC, CORP
Firm Phone: 718-956-6341  Firm Address: 45-14 251ST SUITE 127 LITTLENECK NY 11362 

Work Started or Filed by Others: YES
Work Category:   N - NEW BUILDING Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $145.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PHILLIP MORROW
Owner Business Name: BRONX NY E 188 ST APTS LP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600 A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/27/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REPAIRING OBJECTIONS ON PERMIT APPLICATION Y158823.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y180361
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/23/2016 12/27/2016 JRP V (35) (1)
INSPECTION COMMENTS: FAIL
 
(2) 12/29/2016 12/30/2016 PDI C R (30) (0)
INSPECTION COMMENTS: CONTRACTOR SENT PHOTOS OF FUSES CHANGES TO INSPECTOR JOFFREE PENA , I CONFIRMED WITH INSPECTOR PENNA , ALL OKAY

OBJECTION FOR APPLICATION #: Y180361
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) NOT ALL THE SAME FUSES 240.3
RSLV 12/23/2016 12/23/2016 12/29/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order