| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
1 |
2 SETS OF 500 MCM |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
2 SETS OF 500 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
26 |
8-16 CKT. PANEL |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
12/24 CKT. PANEL |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (ALL FLOORS)ALL HEATHERS IN BATHROOMS NOT LISTED FOR WET OR DAMP LOCATION110.3(B) |
RSLV |
06/21/2018 |
06/21/2018 |
07/11/2018 |
| |
| 002 |
(999) |
OTHER (ALL FLOORS)BURIED BOX IN CEILING IN ALL WATER HEATHER ROOMS 314.29 |
RSLV |
06/21/2018 |
06/21/2018 |
07/11/2018 |
| |
| 003 |
(999) |
OTHER (ALL FLOORS) ALL STOVES FRAME NOT GROUNDED 250.140 |
RSLV |
06/21/2018 |
06/21/2018 |
07/11/2018 |
| |
| 004 |
(999) |
OTHER (BASEMENT) NO WORKING SPACE FOR ENTIRE ELECTRICAL ROOM 110.26(A) |
RSLV |
06/21/2018 |
06/21/2018 |
07/11/2018 |
| |
| 005 |
(999) |
OTHER (BASEMENT) ELECTRICAL ROOM NOT FIRE RATED 110.31 |
RSLV |
06/21/2018 |
06/21/2018 |
07/11/2018 |
| |
| 006 |
(999) |
OTHER (BASEMENT) NO GEC FOR BOTH SERVICES 250.66 |
RSLV |
06/21/2018 |
06/21/2018 |
07/19/2018 |
| |
| 007 |
(999) |
OTHER (BASEMENT) UNDERSIZE WIRE FOR 200 AMP SERVICE 310.16 |
RSLV |
06/21/2018 |
06/21/2018 |
07/11/2018 |
| |
| 008 |
(999) |
OTHER (BASEMENT) NEED LOAD CALCULATION FOR SERVICE 220.40O0 |
RSLV |
06/21/2018 |
06/21/2018 |
07/19/2018 |
| |
| 009 |
(999) |
OTHER (GROUND FLOOR) OUTSIDE GFCI NOT WR 406.8(B) |
RSLV |
06/21/2018 |
06/21/2018 |
07/11/2018 |
| |
| 010 |
(999) |
OTHER (ALL FLOORS) SPLICE BOX IN WATER HEATER ROOM NOT BONDED 314.4 |
RSLV |
07/11/2018 |
07/11/2018 |
07/19/2018 |
| |
| 011 |
(999) |
OTHER (BASEMENT) LB CONDULETS BURIED 314.29 |
RSLV |
07/11/2018 |
07/11/2018 |
07/19/2018 |