BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y180089
Premises: 712 EAST 175 STREET BRONX BIN: 2129012     Block: 2948   Lot: 9
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 712 E 175 ST Census Tract:   369.02 Health Area:  1900
BASEMENT AND 1- 7 FLOOR Admin Area:   Y - BRONX Inspection Area:   I
BRONX, NY 10457 Community Board:   206
Related Job Number:    220520498
DOB Cross Street(s):   CROTONA AVENUE,    CLINTON AVENUE
Status:   C - JOB IS SIGNED OFF 09/29/2018 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/14/2016 9:00 PM
Application Entered:   11/14/2016 Job Start Date:   11/14/2016
Last Change:   09/29/2018 Job End Date:   09/12/2017
Appointment Status:   
Last Inspection By:   GIUSEPPE IMBURGIA       On     07/19/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012724 Licensee Name: JUAN C ASCUASIATI
Firm: 004563 Firm Name: ASCUATECH ELECTRICAL CORP
Firm Phone: 718-583-2519  Firm Address: 448 EAST 173RD STREET BRONX NY 10457 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
Total Fee:  $981.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LIN GUANG
Owner Business Name: C &P REALTY OF NYC LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  2 SETS OF 500 MCM
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  2 SETS OF 500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  26  8-16 CKT. PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  12/24 CKT. PANEL
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                   
LOB                   
001  1-2  16  32               
002  1-4  32  64  16               
003  1-4  32  64  16               
004  1-4  32  64  16               
005  1-4  32  64  16               
006  1-4  32  64  16               
007  1-4  32  64  16               
ROF                       
Buildings Total 223  428  52  111                  
Total Units : 814 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 26 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 27 - Removed Meters 0 = Total Meters 27

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/14/2016 Notice: 1 - FIRST NOTICE 07/13/2018
Power Issued: 11/14/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW SERVICE AND NEW WIRING .

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y180089
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/21/2018 06/22/2018 JRP V (60) (9)
INSPECTION COMMENTS: CONTRACTOR NEED TO FILE FOR MISSING 200 AMP SERVICE AND FEEDER AND FIRE ALARM DISCONNECT
 
(2) 07/11/2018 07/13/2018 JRP V Y (30) (2)
INSPECTION COMMENTS: FAIL
 
(3) 07/19/2018 07/20/2018 GIG C R (38) (0)
INSPECTION COMMENTS: INSPECTION PASSED

OBJECTION FOR APPLICATION #: Y180089
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)ALL HEATHERS IN BATHROOMS NOT LISTED FOR WET OR DAMP LOCATION110.3(B)
RSLV 06/21/2018 06/21/2018 07/11/2018
 
002 (999) OTHER
(ALL FLOORS)BURIED BOX IN CEILING IN ALL WATER HEATHER ROOMS 314.29
RSLV 06/21/2018 06/21/2018 07/11/2018
 
003 (999) OTHER
(ALL FLOORS) ALL STOVES FRAME NOT GROUNDED 250.140
RSLV 06/21/2018 06/21/2018 07/11/2018
 
004 (999) OTHER
(BASEMENT) NO WORKING SPACE FOR ENTIRE ELECTRICAL ROOM 110.26(A)
RSLV 06/21/2018 06/21/2018 07/11/2018
 
005 (999) OTHER
(BASEMENT) ELECTRICAL ROOM NOT FIRE RATED 110.31
RSLV 06/21/2018 06/21/2018 07/11/2018
 
006 (999) OTHER
(BASEMENT) NO GEC FOR BOTH SERVICES 250.66
RSLV 06/21/2018 06/21/2018 07/19/2018
 
007 (999) OTHER
(BASEMENT) UNDERSIZE WIRE FOR 200 AMP SERVICE 310.16
RSLV 06/21/2018 06/21/2018 07/11/2018
 
008 (999) OTHER
(BASEMENT) NEED LOAD CALCULATION FOR SERVICE 220.40O0
RSLV 06/21/2018 06/21/2018 07/19/2018
 
009 (999) OTHER
(GROUND FLOOR) OUTSIDE GFCI NOT WR 406.8(B)
RSLV 06/21/2018 06/21/2018 07/11/2018
 
010 (999) OTHER
(ALL FLOORS) SPLICE BOX IN WATER HEATER ROOM NOT BONDED 314.4
RSLV 07/11/2018 07/11/2018 07/19/2018
 
011 (999) OTHER
(BASEMENT) LB CONDULETS BURIED 314.29
RSLV 07/11/2018 07/11/2018 07/19/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.