Electrical Application Details for App #: Y179069
Premises: 932 SOUTHERN BOULEVARD BRONX BIN: 2005884     Block: 2735   Lot: 14
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 932 SOUTHERN BLVD Census Tract:   89 Health Area:  3700
ALL FLOORS Admin Area:   Y - BRONX Inspection Area:   C
BRONX, NY 10459 Community Board:   202
DOB Cross Street(s):   BARRETTO STREET,    EAST 163 STREET
Status:   C - JOB IS SIGNED OFF 04/17/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/24/2016 3:38 PM
Application Entered:   08/24/2016 Job Start Date:   08/24/2016
Last Change:   04/17/2018 Job End Date:   12/30/2017
Appointment Status:   
Last Inspection By:   GIUSEPPE IMBURGIA       On     04/16/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009784 Licensee Name: STANLEY MURRAY
Firm: 000576 Firm Name: GEMINI ELECTRIC CO., INC.
Firm Phone: 718-654-6700  Firm Address: 2460 WILLIAMSBRIDGE ROAD.2ND BRONX NY 10469-4806 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $576.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   GYM/RESTAURANT/STORE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT RUBINO
Owner Business Name: AB CAPSTONE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    15             
001    27             
002    85  80    10           
003    63  42             
Buildings Total 190  134    18                
Total Units : 350 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 3 #10-Wire 1
Existing Meters 1 + New Meters 4 - Removed Meters 0 = Total Meters 5

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/24/2016 Notice: 1 - FIRST NOTICE 02/16/2018
Power Issued: 08/24/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  UPGRADING THE SERVICE AND COMPLETE REWIRING FOR BLINK FITNESS ON SECOND AND THIRD FLOOR

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y179069
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/16/2018 02/16/2018 EVG V (69) (4)
INSPECTION COMMENTS: JOB FAILED, ALL TEMPORARY WIRES FROM CON ED MUST BE REMOVED BEFORE FINAL CERTIFICATION.
 
(2) 04/16/2018 04/16/2018 GIG C R (43) (0)
INSPECTION COMMENTS: INSPECTION PASSED

OBJECTION FOR APPLICATION #: Y179069
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(FLOOR: 002)IN THE 2ND FLOOR ELECTRICAL ROOM ALL BUCKET FEEDING AC UNITS ON THEROOF ARE OVER FUSED AT 150 A, BUT SHOULD BE 100 A.
RSLV 02/16/2018 02/16/2018 04/16/2018
 
002 ( 30) OUTLET BOXES ARE NOT SECURED
(ALL FLOORS) ALL 2X2 FIXTURES IN DROP CEILINGS NEED TO BE SUPPORTED.
RSLV 02/16/2018 02/16/2018 04/16/2018
 
003 (999) OTHER
(BASEMENT)SERVICE IS NOT COMPLETELY WIRED DUE TO A CON EDISON ISSUE.
RSLV 02/16/2018 02/16/2018 04/16/2018
 
004 (999) OTHER
(ROOF)BOTH RECEPTACLES ON THE ROOF FOR SERVICE PURPOSES FOR THE AC UNITSNEED TO BE WR/TR AND HAVE IN USE COVERS.
RSLV 02/16/2018 02/16/2018 04/16/2018