| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
400 AMPS |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
4 |
#3 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
300 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
5 |
4-100AMPS,1-200 AMPS |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH (BASEMENT) 200 AMP PANEL |
RSLV |
11/21/2016 |
11/21/2016 |
12/16/2016 |
| |
| 002 |
(137) |
GROUNDING ELECTRODE CONDUCTOR IS NOT OF PROPER SIZE FOR SERVICE (BASEMENT) GEC INCORRECT SIZE |
RSLV |
11/21/2016 |
11/21/2016 |
12/16/2016 |
| |
| 003 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (BASEMENT) 300 AMP FUSED DISCONNECT FEEDING 200 AMP RATED PANEL |
RSLV |
11/21/2016 |
11/21/2016 |
12/16/2016 |
| |
| 004 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (BASEMENT) PANEL CONCENTRIC KOS PROPERLY CLOSED |
RSLV |
11/21/2016 |
11/21/2016 |
12/16/2016 |
| |
| 005 |
(356) |
RACEWAY LACKS MECHANICAL CONTINUITY (BASEMENT)200 AMP PANEL CONDUITS INSTALLED ON DEFECTIVE CONCENTRIC KOS |
RSLV |
11/21/2016 |
11/21/2016 |
12/16/2016 |
| |
| 006 |
(999) |
OTHER (BASEMENT) MORE THEN 3 CURRENT CARRYING CONDUCTORS 310.15(2)(A) |
RSLV |
11/21/2016 |
11/21/2016 |
12/16/2016 |
| |
| 007 |
(999) |
OTHER (BASEMENT) MULTI BRANCH WIRE CIRCUITS NOT GROUPED 210.46 |
RSLV |
11/21/2016 |
11/21/2016 |
12/16/2016 |
| |
| 008 |
(999) |
OTHER (BASEMENT)STEAM PIPES LOCATED DIRECTLY OBOVE ELECTRICAL EQUIPMENT 110.26 |
RSLV |
11/21/2016 |
11/21/2016 |
12/16/2016 |
| |
| 009 |
(999) |
OTHER (BASEMENT) NO ARC FLASH WARNING STICKERS 110.16 |
RSLV |
11/21/2016 |
11/21/2016 |
12/16/2016 |