Electrical Application Details for App #: Y178751
Premises: 1848 ANTHONY AVENUE BRONX BIN: 2007583     Block: 2803   Lot: 7
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1848 ANTHONY AV Census Tract:   233.02 Health Area:  2310
THROUGHOUT Admin Area:   Y - BRONX Inspection Area:   E
BRONX, NY 10457 Community Board:   205
DOB Cross Street(s):   MOUNT HOPE PLACE,    EAST TREMONT AVENUE
Status:   C - JOB IS SIGNED OFF 12/27/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/02/2016 9:45 PM
Application Entered:   08/02/2016 Job Start Date:   08/03/2016
Last Change:   12/27/2016 Job End Date:   08/03/2017
Appointment Status:   
Last Inspection By:   JOFFRE PENA       On     12/16/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009968 Licensee Name: SIGMOND FRIED
Firm: 000558 Firm Name: FRIED ELECTRIC CO.
Firm Phone: 718-389-2141  Firm Address: 67 WEST STREET, UNIT 321 BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $537.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   HOMELESS SHELTER
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID SOMERSTEIN
Owner Business Name: SOMERSTEIN ASSOCIATES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400 AMPS
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  #3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  300 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  5  4-100AMPS,1-200 AMPS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001        10                 
002        10                 
003        10                 
004        10                 
Buildings Total     40                    
Total Units : 40 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/02/2016 Notice: 1 - FIRST NOTICE 11/22/2016
Power Issued: 08/02/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  THIS IS USED AS A HOMELESS SHELTER. WE ARE INSTALLING ONE (1) A/C OUTLET IN EACH OF 40 ROOMS.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y178751
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/21/2016 11/22/2016 GIG V (60) (9)
INSPECTION COMMENTS: INSPECTION FAILED OBJECTIONS ISSUED( INSPECTED SERVICE ONLY) MUST CHECK WHOLE JOB OVER
 
(2) 12/16/2016 12/16/2016 JRP C R (40) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED. JOB COMPLETE.

OBJECTION FOR APPLICATION #: Y178751
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(BASEMENT) 200 AMP PANEL
RSLV 11/21/2016 11/21/2016 12/16/2016
 
002 (137) GROUNDING ELECTRODE CONDUCTOR IS NOT OF PROPER SIZE FOR SERVICE
(BASEMENT) GEC INCORRECT SIZE
RSLV 11/21/2016 11/21/2016 12/16/2016
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) 300 AMP FUSED DISCONNECT FEEDING 200 AMP RATED PANEL
RSLV 11/21/2016 11/21/2016 12/16/2016
 
004 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(BASEMENT) PANEL CONCENTRIC KOS PROPERLY CLOSED
RSLV 11/21/2016 11/21/2016 12/16/2016
 
005 (356) RACEWAY LACKS MECHANICAL CONTINUITY
(BASEMENT)200 AMP PANEL CONDUITS INSTALLED ON DEFECTIVE CONCENTRIC KOS
RSLV 11/21/2016 11/21/2016 12/16/2016
 
006 (999) OTHER
(BASEMENT) MORE THEN 3 CURRENT CARRYING CONDUCTORS 310.15(2)(A)
RSLV 11/21/2016 11/21/2016 12/16/2016
 
007 (999) OTHER
(BASEMENT) MULTI BRANCH WIRE CIRCUITS NOT GROUPED 210.46
RSLV 11/21/2016 11/21/2016 12/16/2016
 
008 (999) OTHER
(BASEMENT)STEAM PIPES LOCATED DIRECTLY OBOVE ELECTRICAL EQUIPMENT 110.26
RSLV 11/21/2016 11/21/2016 12/16/2016
 
009 (999) OTHER
(BASEMENT) NO ARC FLASH WARNING STICKERS 110.16
RSLV 11/21/2016 11/21/2016 12/16/2016