BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y178669
Premises: 135 ALEXANDER AVENUE BRONX BIN: 2128217     Block: 2309   Lot: 26
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 135 ALEXANDER AV Census Tract:   19 Health Area:  4700
CELLAR, 1ST,2ND,3RD,4TH FLOORS Admin Area:   Y - BRONX Inspection Area:   A
BRONX, NY 10454 Community Board:   201
Related Job Number:    220151065
DOB Cross Street(s):   BRUCKNER BOULEVARD,    EAST 134 STREET
Status:   C - JOB IS SIGNED OFF 04/03/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/26/2016 2:19 PM
Application Entered:   07/26/2016 Job Start Date:   07/28/2016
Last Change:   04/03/2018 Job End Date:   01/31/2017
Appointment Status:   
Last Inspection By:   GIUSEPPE IMBURGIA       On     04/02/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010641 Licensee Name: WILLIE THROWER, JR.
Firm: 002858 Firm Name: NOBLE ELECL CONTRG CO INC
Firm Phone: 718-299-9472  Firm Address: 1794 CLINTON AVENUE BRONX NY 10457 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $475.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 5 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSH WEISSMAN
Owner Business Name: JCAL DEVELOPMENT GROUP
Authorized Representative:  JOSH WEISSMAN
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  3  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  5  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    10      10             
001  STORE               
002  #1&#2  14  22    14  14             
003  #3  11  22    11  11             
004  #4&#5  14  22    14  14             
Buildings Total 50  68    45  50                
Total Units : 213 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 6 #4-Wire 2 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/26/2016 Notice: C - CALL TO OFFICE 11/24/2017
Power Issued: 07/26/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y178669
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/16/2017 11/17/2017 JRP V (45) (5)
INSPECTION COMMENTS: NEED TO REFILE APP FOR TOTAL METERS
 
(2) 11/20/2017 11/24/2017 PDI H X (60) (0) Y
INSPECTION COMMENTS: NO PROGRESS ON PAST OBJECTIONS , CONTRACTOR NEEDS TO ADD TO WORK DESCRIPTION.
 
(3) 04/02/2018 04/03/2018 GIG C R (40) (0)
INSPECTION COMMENTS: INSPECTION PASSED

OBJECTION FOR APPLICATION #: Y178669
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) NO GFCI T/O BASEMENT 210.8(A)(2)
RSLV 11/16/2017 11/16/2017 04/02/2018
 
002 (999) OTHER
(BASEMENT) NO GEC 250.66
RSLV 11/16/2017 11/16/2017 04/02/2018
 
003 (999) OTHER
(BASEMENT)PLP PANEL NEEDS DERATING FOR GENERAL WIRING 310.15(B)(2(A)
RSLV 11/16/2017 11/16/2017 04/02/2018
 
004 (999) OTHER
(BASEMENT)IN ALL APARTMENTS STOVE OUTLET AND WALL OUTLETS IN SAME CIRCUIT210.52(B)(2
RSLV 11/16/2017 11/16/2017 04/02/2018
 
005 (999) OTHER
(GROUND FLOOR) NO SHOW WINDOW RECEPTACLES IN BOTH BUSINESS 210.62
RSLV 11/16/2017 11/16/2017 04/02/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.