BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y178534
Premises: 98 EAST BURNSIDE AVENUE BRONX BIN: 2007948     Block: 2829   Lot: 45
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 88 E BURNSIDE AV Census Tract:   241 Health Area:  1600
BSMT, & GROUND FLOOR Admin Area:   Y - BRONX Inspection Area:   F
BRONX, NY 10453 Community Board:   205
DOB Cross Street(s):   WALTON AVENUE,    MORRIS AVENUE
Status:   C - JOB IS SIGNED OFF 12/28/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/16/2016 7:29 PM
Application Entered:   07/16/2016 Job Start Date:   07/16/2016
Last Change:   12/28/2016 Job End Date:   07/16/2017
Appointment Status:   
Last Inspection By:   JOFFRE PENA       On     12/02/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012324 Licensee Name: GERBERT BONHOMME
Firm: 004105 Firm Name: SUPREME ELECTRIC CORP
Firm Phone: 718-658-1078  Firm Address: 107-54 SUTPHIN BLVD JAMAICA NY 11435 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $69.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   K1-STORE BUILDING
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: AJAY PARIKH
Owner Business Name: BRONX WINGS ONE LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  COMPRESSOR & WALK IN FREE
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
GND    15  15    10         
Buildings Total 21  21    15              
Total Units : 65 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/18/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRING FOR A CHICKEN WIN STORE AND ADDING WALKING FREEZER

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y178534
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/17/2016 11/18/2016 GIG V (88) (5)
INSPECTION COMMENTS: MUST CHECK JOB OVER (LANDLORD PROVIDED 2 PANELS AND SERVICE PANELS AND SERVICE ARE INCORRECTLY WIRED LANDLORD HAS ANOTHER ELECTRICIAN FIXING THE SERVICE AND PANELS APP. # Y180148
 
(2) 12/02/2016 12/05/2016 JRP C R (25) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED JOB COMPLETE.

OBJECTION FOR APPLICATION #: Y178534
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(GROUND FLOOR) BOTH PANELS
RSLV 11/17/2016 11/17/2016 12/02/2016
 
002 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
(GROUND FLOOR) BOTH PANELS
RSLV 11/17/2016 11/17/2016 12/02/2016
 
003 (286) NO GFCI IN COMMERCIAL KITCHEN
(GROUND FLOOR) ALL PREP AREAS
RSLV 11/17/2016 11/17/2016 12/02/2016
 
004 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(GROUND FLOOR) KOS OPEN IN PANELS
RSLV 11/17/2016 11/17/2016 12/02/2016
 
005 ( 40) LOCKNUTS ARE MISSING OR LOOSE
(GROUND FLOOR) IN PANEL
RSLV 11/17/2016 11/17/2016 12/02/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back