Electrical Application Details for App #: Y178028
Premises: 285 EAST 138 STREET BRONX BIN: 2000689     Block: 2314   Lot: 10
   

DOB NOW: Inspections


Filed: 285 E 138TH ST Census Tract:   39 Health Area:  4500
BASEMENT, 1 - 11 FLOORS Admin Area:   Y - BRONX Inspection Area:   A
BRONX, NY 10454 Community Board:   201
Related Job Number:    220462407
DOB Cross Street(s):   LINCOLN AVENUE,    ALEXANDER AVENUE
Status:   K - CLOSED/CANCELLED 03/07/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/08/2016 7:46 PM
Application Entered:   06/08/2016 Job Start Date:   06/08/2016
Last Change:   03/07/2019 Job End Date:   07/08/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     03/06/2019      
Field Disp:   K - OK TO CANCEL
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011252 Licensee Name: ALBERT DATTOLO
Firm: 001211 Firm Name: RAINBOW ELECTRIC CO., INC
Firm Phone: 718-521-0926  Firm Address: 76-18 ROCKAWAY BLVD WOODHAVEN NY 11421 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $4,105.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JENNIFER STEINBERG
Owner Business Name: WEST SIDE FEDERATION FOR
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  30  60
B. 101 Up to 200 AMPS  5  200
C. 201 Up to 600 AMPS  3  400
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  5  1,6,10
B. Over #2 to 1/0  6  1/0,
C. Over 1/0 to 250 MCM  2  250,3/0
D. Over 250 MCM  17  500,400,300
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    25  10    25  50  10  50         
001    25  25    25  50  10         
002  25  420  140  70             
003  25  420  140  70             
004  25  420  140  70             
005  25  420  140  70             
006  25  360  140  70             
007  25  360  140  70             
008  25  360  140  70             
009  25  360  140  70             
010  10  25  360  140  70             
011  11  25  360  140  70             
ROF    25  10    10  10  30  400         
Buildings Total 325  3885  30  1460  810     460           
Total Units : 6970 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 121 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 121 - Removed Meters 0 = Total Meters 121

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/08/2016 Notice: 1 - FIRST NOTICE 01/29/2019
Power Issued: 06/08/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW COMSTRUCTION OF 121 APARTMENT COMPLEX WITH REC ROOM, LAUNDRY ROOM .11 STORIES WITH 1 BASEMENT .

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y178028
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/13/2018 09/14/2018 GYM V (120) (5)
INSPECTION COMMENTS: SEE APP # X0079095 X00079121
 
(2) 01/29/2019 01/29/2019 JRP V Y (50) (1)
INSPECTION COMMENTS: FAIL
 
(3) 02/23/2019 02/25/2019 GYM J R (115) (0)
INSPECTION COMMENTS: WITHDRAWAL REQUIRED SEE APP # X00079095 X00079121 X00078073
 
(4) 03/06/2019 03/07/2019 CLC K (3) (0) Y
INSPECTION COMMENTS: OK TO CANCEL REFER TO APP# X0013416 X00129725

OBJECTION FOR APPLICATION #: Y178028
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 004) CABLE SUPPORT NOT LISTED 110.2
RSLV 09/13/2018 09/13/2018 02/23/2019
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ALL FLOORS) PANELS ELECTRIC CLOSETS.
RSLV 09/13/2018 09/13/2018 02/23/2019
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) PANELS IN ELECTRIC CLOSETS
RSLV 09/13/2018 09/13/2018 02/23/2019
 
004 ( 30) OUTLET BOXES ARE NOT SECURED
(ROOF) HVAC DISC SWITCHES.
RSLV 09/13/2018 09/13/2018 02/23/2019
 
005 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ROOF) ZIP SCREWS HVAC DISC SWITCHES.
RSLV 09/13/2018 09/13/2018 01/29/2019
 
006 (999) OTHER
(FLOOR: 011) MISSING CABLE SUPPORT AT END OF CONDUITS 300.19
RSLV 01/29/2019 01/29/2019 02/23/2019