Electrical Application Details for App #: Y177510
Premises: 1107 HOE AVENUE BRONX BIN: 2006042     Block: 2744   Lot: 39
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1107 HOE AV Census Tract:   127.01 Health Area:  3600
ENTIRE Admin Area:   Y - BRONX Inspection Area:   C
BRONX, NY 10459 Community Board:   202
DOB Cross Street(s):   WEST FARMS ROAD,    EAST 167 STREET
Status:   C - JOB IS SIGNED OFF 12/09/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/05/2016 10:33 AM
Application Entered:   05/05/2016 Job Start Date:   05/05/2016
Last Change:   12/09/2016 Job End Date:   05/05/2017
Appointment Status:   
Last Inspection By:   FATA, LUIGI       On     11/04/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010190 Licensee Name: ABE HIMELFARB
Firm: 002663 Firm Name: ALEF ELEC'L CONTR'G INC
Firm Phone: 212-764-2200  Firm Address: 247 WEST 38TH STREET NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $356.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GEORGE ZAGREDA
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  6  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  7  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
SWK                     
SWL                     
001  1F  10  25    10  10             
001  1R  10  25    10  10             
002  2F  10  25    10  10             
002  2R  10  25    10  10             
003  3F  10  25    10  10             
003  3R  10  25    10  10             
Buildings Total 75  156    68  75                
Total Units : 374 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 7 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/05/2016 Notice: 1 - FIRST NOTICE 09/06/2016
Power Issued: 05/05/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRE FOR SIX GAS FIRED BOILERS; INST 12 SD.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y177510
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/02/2016 09/06/2016 GIG V (59) (8)
INSPECTION COMMENTS: FAIL.
 
(2) 11/04/2016 11/07/2016 LUF C R (60) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: Y177510
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (102) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ALL FLOORS) SHEETROCK SCREWS USED IN BATHROOM OUTLETS AND SWITCHES
RSLV 09/02/2016 09/02/2016 11/04/2016
 
002 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(ALL FLOORS) ALL APTS.
RSLV 09/02/2016 09/02/2016 11/04/2016
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) ALL APTS.
RSLV 09/02/2016 09/02/2016 11/04/2016
 
004 (999) OTHER
(ALL FLOORS)ALL BATHROOM OUTLETS AND SWITCHED MORE THEN 1/4" SET BACK 314.20
RSLV 09/02/2016 09/02/2016 11/04/2016
 
005 ( 12) SERVICE CONDUCTORS ARE NOT OF THE PROPER SIZE
(BASEMENT) 2/0 WIRE ON 200 AMP FUSES
RSLV 09/02/2016 09/02/2016 11/04/2016
 
006 ( 53) GFCI HAS NOT BEEN PROVIDED
(BASEMENT) UNFINISHED BASEMENT
RSLV 09/02/2016 09/02/2016 11/04/2016
 
007 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT) LOAD SIDE OF MAIN SWITCH
RSLV 09/02/2016 09/02/2016 11/04/2016
 
008 ( 53) GFCI HAS NOT BEEN PROVIDED
(OPEN SPACE) OUTSIDE
RSLV 09/02/2016 09/02/2016 11/04/2016