BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y176893
Premises: 1160 CROMWELL AVENUE BRONX BIN: 2003023     Block: 2496   Lot: 34
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1160 CROMWELL AV Census Tract:   197 Health Area:  3320
FLOORS 1,2,3,4,5,6 Admin Area:   Y - BRONX Inspection Area:   E
BRONX, NY 10452 Community Board:   204
DOB Cross Street(s):   PEDESTRIAN PATH    
Status:   C - JOB IS SIGNED OFF 04/25/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/16/2016 10:31 AM
Application Entered:   03/16/2016 Job Start Date:   03/17/2016
Last Change:   04/25/2016 Job End Date:   03/15/2017
Appointment Status:   
Last Inspection By:   DIMAGGIO, PHILLIP       On     04/14/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  

License #: 011063 Licensee Name: MELVIN A BRANDL
Firm: 000219 Firm Name: BRANDL ELECTRIC INC.
Firm Phone: 718-327-5677  Firm Address: 250 GREENPOINT AVE 4TH FL BROOKLYN NY 11222 

Removal of ECB Violation(s): 35158907X   35158906Y   35158905M        
Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $65.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: RTERE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  1J               
002  2A               
003  3A               
003  3E               
004  4B               
004  4C               
005  5E               
006  6D               
006  6E               
006  6I               
Buildings Total 20  50    20  20                
Total Units : 110 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REMOVAL OF VIOLATION WORK DONE WITHOUT PERMIT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y176893
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/14/2016 04/14/2016 PDI C (40) (0) Y
INSPECTION COMMENTS: PASS




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order