BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y173830
Premises: 150 WEST 179 STREET BRONX BIN: 2014862     Block: 3221   Lot: 26
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 150 W 179 ST Census Tract:   245.02 Health Area:  1510
BSMT, 1 THRU 6 FL. Admin Area:   Y - BRONX Inspection Area:   F
BRONX, NY 10453 Community Board:   205
DOB Cross Street(s):   ANDREWS AVENUE SOUTH,    LORING PLACE SOUTH
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/14/2015 9:55 AM
Application Entered:   07/14/2015 Job Start Date:   07/14/2015
Last Change:   08/22/2025 Job End Date:   07/14/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   PETER GREENE       On     05/15/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 009802 Licensee Name: PETER J CATANZARO
Firm: 001146 Firm Name: PETER J. CATANZARO, INC.
Firm Phone: 718-832-3230  Firm Address: 126 41ST STREET BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $793.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARSHALL ROSE
Owner Business Name: WESTMAR REALTY GROUP LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  3 PHASE 400A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  4 WIRE #500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  36  1 PHASE 12 POLES
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  1A                   
001  1B                   
001  1C                   
001  1D                   
001  1E                   
001  1F                   
002  2A                   
002  2B                   
002  2C                   
002  2D                   
002  2E                   
002  2F                   
003  3A                   
003  3B                   
003  3C                   
003  3D                   
003  3E                   
003  3F                   
004  4A                   
004  4B                   
004  4C                   
004  4D                   
004  4E                   
004  4F                   
005  5A                   
005  5B                   
005  5C                   
005  5D                   
005  5E                   
005  5F                   
006  6A                   
006  6B                   
006  6C                   
006  6D                   
006  6E                   
006  6F                   
Buildings Total   108  36                    
Total Units : 144 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 37 + New Meters 37 - Removed Meters 37 = Total Meters 37

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 07/14/2015 Notice: 1 - FIRST NOTICE 05/16/2017
Power Issued: 07/14/2015 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y173830
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/05/2017 01/06/2017 PDI J (90) (0) Y
INSPECTION COMMENTS: JOB STILL IN PROGRESS ,PAST ECB VIOLATION ON JOB , CONTRACTOR HAS 12/3 MULTI WIRE IN PANEL NEEDS TWO POLE NREAKERS .
 
(2) 01/17/2017 01/17/2017 GIG N (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR DID NOT KNOW OF INSPECTION
 
(3) 01/24/2017 01/24/2017 GIG C (43) (0) Y
INSPECTION COMMENTS: INSPECTION PASSED
 
(4) 05/15/2017 05/16/2017 PGR V (75) (7)
INSPECTION COMMENTS: RE INSPECT ALL APT

OBJECTION FOR APPLICATION #: Y173830
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 003) OPEN EXPOSED MC CABLE RUN IN APT 3B
OPEN 05/15/2017 05/15/2017
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 003)EXPOSED CONDUCTOR WITH NO DEICES CONNECTED TO OVERCURRENTPROTECTION. APT 3B
OPEN 05/15/2017 05/15/2017
 
003 ( 29) OUTLET BOXES ARE NOT COVERED
(FLOOR: 003) KITCHEN AND LIVING ROOM APT 3B
OPEN 05/15/2017 05/15/2017
 
004 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 005)APT 5 D. TWO SEPARATE CIRCUIT ON SAME DEVICE( RING CIRCUIT ).
OPEN 05/15/2017 05/15/2017
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(FLOOR: 005) GROUND WIRE FROM MC CABLE IN PANEL APT 5D
OPEN 05/15/2017 05/15/2017
 
006 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 005) APT 5D
OPEN 05/15/2017 05/15/2017
 
007 (999) OTHER
(FLOOR: 006) ALL FLOOR PROVIDE LISTING FOR WIRE WAY IN STAIRWAY.
OPEN 05/15/2017 05/15/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order