BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y171236
Premises: 525 EAST 137 STREET BRONX BIN: 2000053     Block: 2265   Lot: 59
   
Application Completed and Certified

Filed: 535 E 137 ST Census Tract:   25 Health Area:  4500
BSMT & GROUND FL. Admin Area:   Y - BRONX Inspection Area:   A
BRONX, NY 10454 Community Board:   201
Special Place Name:   TENDER TOTS CHILD CARE CENTER
Related Job Number:    220406790
DOB Cross Street(s):   BROOK AVENUE,    ST ANNS AVENUE
Status:   C - JOB IS SIGNED OFF 09/03/2015 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/03/2014 9:40 PM
Application Entered:   12/03/2014 Job Start Date:   12/04/2014
Last Change:   09/03/2015 Job End Date:   12/04/2015
Appointment Status:   
Last Inspection By:   SCHIAVO, JAMES       On     08/28/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010765 Licensee Name: CESAR QUERY
Firm: 002004 Firm Name: C.Q. ELECTR'L CONTRG CORP
Firm Phone: 718-204-9255  Firm Address: 723 EAST 135TH STREET BRONX NY 10454 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $186.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  220406790
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHAIM WEISS
Owner Business Name: STERLING EDUCATION
Authorized Representative:  JOSE TOLENTINO
Relationship To Owner:   CONSTRUCTION MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMP. 3 PHASE
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4#3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200 AMP. 3 PHASE 42 CIRC.
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND  DAY C  30  20    10  30         
Buildings Total 30  20    10  30              
Total Units : 97 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/03/2014 Notice: C - CALL TO OFFICE 08/13/2015
Power Issued: 12/03/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  DOB-2K14-113 ADDRESS A.K.A. 525 E 137 ST.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y171236
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/21/2015 07/24/2015 JSV A G (65) (6) Y
INSPECTION COMMENTS: VIOL
 
(2) 08/12/2015 08/13/2015 PDI H X E (30) (0) Y
INSPECTION COMMENTS: STILL IN PROGRESS
 
(3) 08/28/2015 09/02/2015 JSV C R E (30) (0) Y
INSPECTION COMMENTS: CERT

OBJECTION FOR APPLICATION #: Y171236
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
1FL/NEUTRAL BONDED AFTER S.S/250.24.5
RSLV 07/21/2015 08/12/2015 08/28/2015
 
002 (999) OTHER
1FL/NO GFCI PROVIDED FOR CLASSROOM WITHIN 6' OF SINKS,210.8-527.6
RSLV 07/21/2015 08/12/2015 08/28/2015
 
003 (999) OTHER
CELLAR/NO SECONDARY GROUNED PROVIDED FOR S.S 250.53,D2
RSLV 07/21/2015 08/12/2015 08/28/2015
 
004 (999) OTHER
1FL/NO HANDLE TIES PROVIDED FOR MULTI BRANCH CIRCUIT 210.4
RSLV 07/21/2015 08/12/2015 08/28/2015
 
005 (999) OTHER
1FL/DOUBLE LUGGED IN PANEL 110.3B
RSLV 07/21/2015 08/12/2015 08/28/2015
 
006 (999) OTHER
CELLAR/SS N OT BONDED PROPERLY 250.640/MULTI SS NOT BONDED AS PERCODE
RSLV 07/21/2015 08/12/2015 08/28/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order