BIS Menu  |  Bldg Info Search  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y169628
Premises: 1024 SOUTHERN BOULEVARD BRONX BIN: 2130444     Block: 2743   Lot: 6
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1018 SOUTHERN BLVD Census Tract:   119 Health Area:  2900
1 FLOOR Admin Area:   Y - BRONX Inspection Area:   C
BRONX, NY 10459 Community Board:   202
DOB Cross Street(s):       
Status:   C - JOB IS SIGNED OFF 09/29/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/31/2014 1:24 PM
Application Entered:   07/31/2014 Job Start Date:   08/02/2014
Last Change:   09/29/2020 Job End Date:   10/23/2014
Appointment Status:   
Last Inspection By:   GIUSEPPE IMBURGIA       On     09/29/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010759 Licensee Name: YOUNG S CHOE
Firm: 001995 Firm Name: Y.S ELECTRIC
Firm Phone: 866-863-4448  Firm Address: 129-09 26TH AVENUE, #103 FLUSHING NY 11354 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $67.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   GARMENTS STORE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOHN LEE
Owner Business Name: GARMENT STORE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    12  15    70  15         
Buildings Total 12  15    70     15           
Total Units : 118 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/13/2020
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RENOVATIONS.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y169628
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/13/2015 05/18/2015 PDI J (20) (0) Y
INSPECTION COMMENTS: JOB IN PROGRESS
 
(2) 06/04/2015 06/06/2015 JSV N (30) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(3) 09/11/2020 09/13/2020 JRP V (60) (5)
INSPECTION COMMENTS: INSPECTION COMPLETED
 
(4) 09/29/2020 09/29/2020 GIG C R (41) (0)
INSPECTION COMMENTS: INSPECTION PASSED

OBJECTION FOR APPLICATION #: Y169628
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(GROUND FLOOR) NO SHOW WINDOW RECEPTACLE 210.62
RSLV 09/11/2020 09/11/2020 09/29/2020
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(GROUND FLOOR) MULTI BRANCH CIRCUITS NEEDS HANDLE TIES 219.4(B)
RSLV 09/11/2020 09/11/2020 09/29/2020
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(GROUND FLOOR)EQUIPMENT GROUND FOR A/C DISCONNECT UNDERSIZE FOR 50 AMPSOVERCURRENT PROTECTION 250.122
RSLV 09/11/2020 09/11/2020 09/29/2020
 
004 (307) NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT
(GROUND FLOOR) NO SERVICE OUTLET FOR A/C UNIT 210.63
RSLV 09/11/2020 09/11/2020 09/29/2020
 
005 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(GROUND FLOOR) NEED TO PROVIDE DIRECTORY 408.4
RSLV 09/11/2020 09/11/2020 09/29/2020



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Bldg Info Search  |  Electrical Inspection Work Order  |  Back