BIS Menu  |  Insp. Results  |  Certs. Occupancy  |  License Query  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y169520
Premises: 2968 JEROME AVENUE BRONX BIN: 2017610     Block: 3320   Lot: 8
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 2968 JEROME AV Census Tract:   407.01 Health Area:  0420
GROUND FLOOR Admin Area:   Y - BRONX Inspection Area:   H
BRONX, NY 10468 Community Board:   207
DOB Cross Street(s):   EAST 199 STREET,    BEDFORD PARK BOULEVARD
Status:   C - JOB IS SIGNED OFF 09/20/2016 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/23/2014 3:28 PM
Application Entered:   07/23/2014 Job Start Date:   07/23/2014
Last Change:   09/20/2016 Job End Date:   12/23/2014
Appointment Status:   
Last Inspection By:   GIUSEPPE IMBURGIA       On     04/27/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012024 Licensee Name: TIMOTHY COLEMAN
Firm: 003668 Firm Name: TIMOTHY COLEMAN LICENSED
Firm Phone: 718-337-0921  Firm Address: 19-14 MOTT AVENUE ELECTRICIAN FAR ROCKAWAY NY 11691 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $319.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   KARATE SCHOOL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHRIS SANTERO
Owner Business Name: LORDAE PROPERTY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  200 AMP SERV SW
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  4 - 3/0 AWG
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  42 CKT MCB
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    30  20  10  30             
002    12    12             
ROF                   
Buildings Total 42  25  15  42              
Total Units : 127 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 0 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/23/2014 Notice: 1 - FIRST NOTICE 04/15/2016
Power Issued: 07/23/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SERVICE WORK AND GENERAL WIRING FOR 2 STORES

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y169520
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/28/2016 01/28/2016 GIG N (35) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW
 
(2) 03/11/2016 03/14/2016 GIG J (30) (0) Y
INSPECTION COMMENTS: FAIL ,NEEDS TO BE INSPECTED AGAIN,
 
(3) 04/07/2016 04/07/2016 PDI N (15) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW
 
(4) 04/14/2016 04/15/2016 GIG V (78) (2)
INSPECTION COMMENTS: INSPECTION FAILED OBJECTIONS ISSUED
 
(5) 04/27/2016 04/28/2016 GIG C R (69) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: Y169520
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 10) BRANCH CIRCUIT CONDUCTORS ARE NOT PROPER SIZE
(FLOOR: 001) 14 WIRE USED IN BOTH PANELS SEE NYC AMENDMENT
RSLV 04/14/2016 04/14/2016 04/27/2016
 
002 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(FLOOR: 001)MC CABLE AND ARMORED CABLE NOT SUPPORTED T-OUT CEILING FIRST ANDSECOND FLOORS
RSLV 04/14/2016 04/14/2016 04/27/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Insp. Results  |  Certs. Occupancy  |  License Query  |  Electrical Inspection Work Order  |  Back