BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y168773
Premises: 2409 BEAUMONT AVENUE BRONX BIN: 2012542     Block: 3090   Lot: 23
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 2409 BEAUMONT AV Census Tract:   389 Health Area:  1100
ALL Admin Area:   Y - BRONX Inspection Area:   I
BRONX, NY 10458 Community Board:   206
DOB Cross Street(s):   EAST 187 STREET,    EAST 188 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/29/2014 6:43 PM
Application Entered:   05/29/2014 Job Start Date:   05/29/2014
Last Change:   08/22/2025 Job End Date:   04/15/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   DIMAGGIO, PHILLIP       On     10/16/2018      
Field Disp:   H - NO PROGRESS ON JOB
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 009747 Licensee Name: MELVYN ZWEBNER
Firm: 002640 Firm Name: ILLUMINOUS ELECTRIC CORP.
Firm Phone: 718-431-1605  Firm Address: 1425 37TH STREET BROOKLYN NY 11218 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $625.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RACHEL SILVER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  24  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 23 #4-Wire 1 #10-Wire 0
Existing Meters 24 + New Meters 24 - Removed Meters 24 = Total Meters 24

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 05/29/2014 Notice: C - CALL TO OFFICE 10/17/2018
Power Issued: 05/29/2014 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y168773
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/28/2017 02/28/2017 PDI N (45) (0) Y
INSPECTION COMMENTS: NO ACCESS, CONTRACTOR NO SHOW.
 
(2) 11/03/2017 11/06/2017 GIG N (15) (0) Y
INSPECTION COMMENTS: SEE APP. # Y177732
 
(3) 11/14/2017 11/15/2017 GIG N (15) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR HE SAID HIS GUYS ARE STUCK IN TRAFFIC
 
(4) 11/30/2017 11/30/2017 JRP V (60) (6)
INSPECTION COMMENTS: FAIL
 
(5) 12/19/2017 12/19/2017 GIG N (26) (0) Y
INSPECTION COMMENTS: CONTRACTOR CANCELLED WITH OFFICE
 
(6) 08/23/2018 08/24/2018 JRP N (10) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR NO SHOW
 
(7) 10/16/2018 10/17/2018 PDI H X (50) (0) Y
INSPECTION COMMENTS: FAIL, THIS JOB STILL HAS NO PROGRESS ON PAST OBJECTIONS ALSO CONTRACTOR STILL HAS ANTHOR APPLICATION FOR NEW SUB FEEDERS AND PANELS AND NEW GFCI OUTLETS TO KITCHEN .....

OBJECTION FOR APPLICATION #: Y168773
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT)MAIN SERVICE DISCONNECT FUSE OVERSIZE 310.16, 310.15(B)(2)(A)
OPEN 11/30/2017 11/30/2017
 
002 (999) OTHER
(BASEMENT) EMT NOT SUPPORTED IN ELECTRICAL ROOM 358.30
OPEN 11/30/2017 11/30/2017
 
003 (999) OTHER
(BASEMENT) GEC WIRE SUBJECT TO DAMAGE 250.64(B)
OPEN 11/30/2017 11/30/2017
 
004 (999) OTHER
(BASEMENT) ALL AC FEEDERS NOT PROPERLY SUPPORTED T/O BASEMENT 320.30
OPEN 11/30/2017 11/30/2017
 
005 (999) OTHER
(BASEMENT) NEEDS FIRE STOP T/O BASEMENT 300.21
OPEN 11/30/2017 11/30/2017
 
006 (999) OTHER
(BASEMENT)PLUMBING PIPES ABOVE ELECTRICAL METER BANK 110.26(F)(1)(B)
OPEN 11/30/2017 11/30/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.