BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y168515
Premises: 536 EAST 138 STREET BRONX BIN: 2000042     Block: 2265   Lot: 39
   

Filed: 536 E 138 ST Census Tract:   25 Health Area:  4500
APT#2W Admin Area:   Y - BRONX Inspection Area:   A
BRONX, NY 10454 Community Board:   201
DOB Cross Street(s):   BROOK AVENUE,    ST ANNS AVENUE
Status:   C - SIGNOFF IS AWAITING FEE PAYMENT 05/06/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/12/2014 7:20 AM
Application Entered:   05/12/2014 Job Start Date:   05/12/2014
Last Change:   05/06/2015 Job End Date:   06/12/2014
Appointment Status:   
Last Inspection By:   SCHIAVO, JAMES       On     04/28/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011282 Licensee Name: STEVEN CRAWLEY
Firm: 002684 Firm Name: RENAISSANCE ELECTRIC CORP
Firm Phone: 718-515-2853  Firm Address: 2359 WESTCHESTER AVENUE BRONX NY 10461 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
5 - FIRE DAMAGE
6 - GENERAL WIRING
Total Fee:  $87.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MOHAMED SHUAIBI
Owner Business Name: SHABAN INC.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  12/24 MLP
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  2W  12  23             
Buildings Total 12  23                
Total Units : 48 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/02/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y168515
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/29/2014 06/02/2014 PDI A (40) (3) Y
INSPECTION COMMENTS: NEW PANEL AND BRAN WIRING DONE,DUE TO PAST FIRE IN APRT 2W
 
(2) 04/28/2015 05/06/2015 JSV C R (40) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: Y168515
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
NEW PANEL/ART 210.4D/NEUTRAL AND PHASES NOT GROUPED
RSLV 05/29/2014 05/29/2014 04/28/2015
 
002 (999) OTHER
A)NEW PANEL/ART 210.4B/MULTI WIRE CIRCUIT NOT DISCONNECTED AT SAMETIME
RSLV 05/29/2014 05/29/2014 04/28/2015
 
003 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
NEW PANEL/KNOCKOUTS MISSING IN NEW PANEL ON TOP
RSLV 05/29/2014 05/29/2014 04/28/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order