BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y167214
Premises: 1991 UNIVERSITY AVENUE BRONX BIN: 2014698     Block: 3216   Lot: 60
   
Application Completed and Certified

Filed: 86 W 179 ST Census Tract:   245.02 Health Area:  1510
STREET LEVEL Admin Area:   Y - BRONX Inspection Area:   F
BRONX, NY 10453 Community Board:   205
DOB Cross Street(s):   AQUEDUCT WALK BIKE PATH,    ANDREWS AVENUE SOUTH
Status:   C - JOB IS SIGNED OFF 04/08/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/27/2014 9:48 AM
Application Entered:   01/27/2014 Job Start Date:   01/28/2014
Last Change:   04/08/2014 Job End Date:   01/28/2015
Appointment Status:   
Last Inspection By:   SCHIAVO, JAMES       On     03/28/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012114 Licensee Name: MUZAFER ZEKIROSKI
Firm: 003816 Firm Name: Z & Z ELECTRIC INC
Firm Phone: 212-941-4600  Firm Address: 1424 WILLIAMSBRIDGE ROAD BRONX NY 10461 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $46.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   BARBAR SHOP
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: MARO REALTY LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    20  13               
Buildings Total 20  13                  
Total Units : 36 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/21/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLATION LIGHT FIXTURES,SWITCHES AND PLUGS.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y167214
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/10/2014 02/21/2014 JSV V (30) (5) Y
INSPECTION COMMENTS: VIOL
 
(2) 03/28/2014 04/04/2014 JSV C R (15) (0) Y
INSPECTION COMMENTS: CERT

OBJECTION FOR APPLICATION #: Y167214
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
1FL-NO DIRECTORY
RSLV 02/10/2014 02/10/2014 03/28/2014
 
002 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
1FL-FLOURESCENT FIXTURES THRU-OUT,1FL
RSLV 02/10/2014 02/10/2014 03/28/2014
 
003 ( 29) OUTLET BOXES ARE NOT COVERED
1FL-FIXTURES OVER FRONT DOOR
RSLV 02/10/2014 02/10/2014 03/28/2014
 
004 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
1FL-WIRES ENTERING FIXTURES NO CONNECTORS
RSLV 02/10/2014 02/10/2014 03/28/2014
 
005 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
1FL-PANEL,30A BREAKER WITH 12 AWG WIRING
RSLV 02/10/2014 02/10/2014 03/28/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back