| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 3) |
APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE BMST SERVICE EQUIPMENTCOM: 200 AMP SERVICE SWITCH, SERVICE ENTRANCE CONDUCTOR |
OPEN |
01/15/2014 |
01/15/2014 |
|
| |
| 002 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY BSMT GROUND CONDUCTORCOM: NO WATER MAIN GROUND PROVIDED |
OPEN |
01/15/2014 |
01/15/2014 |
|
| |
| 003 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED BSMT SERVICE EQUIPMENTCOM: SERV, ENTRANCE CONDUCTOR, SERVICE SWITCH NEUTRAL BAR NOT BONDED |
OPEN |
01/15/2014 |
01/15/2014 |
|
| |
| 004 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED TO ENCLOSURE |
OPEN |
01/15/2014 |
01/15/2014 |
|
| |
| 005 |
(999) |
OTHER BSMT SERVICE SWITCH. 230COM: SERVICE SWITCH NOT PROPER SIZE |
OPEN |
01/15/2014 |
01/15/2014 |
|
| |
| 006 |
(999) |
OTHER BSMT SERVICE CONDUCTOR NOT PROPER SIZE. 230 |
OPEN |
01/15/2014 |
01/15/2014 |
|
| |
| 007 |
( 19) |
DEFECTIVE WIRING IS IN USE THE ENTIRE BSMTCOM: DEFECTIVE OPEN WIRING ARE IN USE |
OPEN |
01/15/2014 |
01/15/2014 |
|
| |
| 008 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE DEFECTIVE RECEPTACLE ARE IN USE |
OPEN |
01/15/2014 |
01/15/2014 |
|
| |
| 009 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE DEFECTIVE LIGHTING FIXTURES ARE IN USE |
OPEN |
01/15/2014 |
01/15/2014 |
|
| |
| 010 |
( 17) |
DEFECTIVE SWITCHES ARE IN USE DEFECTIVE SWITCH ARE IN USE |
OPEN |
01/15/2014 |
01/15/2014 |
|
| |
| 011 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED ARMORED CABLES ARE NOT PROPERLY SECURED |
OPEN |
01/15/2014 |
01/15/2014 |
|
| |
| 012 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED ARMORED CABLES ARE NOT PROPERLY TERMINATED |
OPEN |
01/15/2014 |
01/15/2014 |
|
| |
| 013 |
( 29) |
OUTLET BOXES ARE NOT COVERED OUTLETS BOXES ARE NOT COVERED |
OPEN |
01/15/2014 |
01/15/2014 |
|
| |
| 014 |
( 39) |
MOTOR NOT PROVIDED WITH PROPER RUNNING PROTECTION OUTLETS BOXES ARE NOT SECURED |
OPEN |
01/15/2014 |
01/15/2014 |
|
| |
| 015 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX KNOCKOUTS ARE NOT CLOSED IN OUTLETS BOXES |
OPEN |
01/15/2014 |
01/15/2014 |
|
| |
| 016 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX KNOCKOUTS ARE NOT CLOSED IN PANEL BOXTHIS IS NOT A FINAL INSPECTION. SEE THIS COMPLAINT #2193900 |
OPEN |
01/15/2014 |
01/15/2014 |
|
| |
| 017 |
(999) |
OTHER "VERY DANGEROUS AND HAZARDOUS CONDITION" |
OPEN |
01/15/2014 |
01/15/2014 |
|