BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y164807
Premises: 280 BAYCHESTER AVENUE BRONX BIN: 2119958     Block: 5141   Lot: 15
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 280 BAYCHESTER AV Census Tract:   462.01 Health Area:  0710
ALL FLOORS SERVED, MR Admin Area:   Y - BRONX Inspection Area:   L
BRONX, NY 10475 Community Board:   210
Related Job Number:    220235751
DOB Cross Street(s):   HUTCHINSON RVR PKWY ET 2 B SB,    NEW ENGLAND THRUWAY NB EXIT 11
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/28/2013 7:02 PM
Application Entered:   06/28/2013 Job Start Date:   08/15/2013
Last Change:   08/22/2025 Job End Date:   08/15/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   URIM SYLA       On     09/02/2014      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 011986 Licensee Name: ANTHONY LUCIANO
Firm: 003652 Firm Name: JAM ELECTRICAL CORP
Firm Phone: 212-265-0142  Firm Address: 1133 6TH AVE 28TH FLOOR NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   G - Garage
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAEL STONE
Owner Business Name: MALL 1 BAY PLAZA LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  ELEVATOR
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 09/08/2014
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  INSTALLATION OF HYDRO ELEVATOR BY ELEVATOR COMPANY IN CONJUNCTION WITH ELEVATOR APPLICATION(273018E).POWER TO CONTROL, 110V LIGHTING, MR,PIT GFCI BY OTHERS.G9567(192)

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y164807
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/02/2014 09/08/2014 UMS A (30) (4) Y
INSPECTION COMMENTS: VOIL

OBJECTION FOR APPLICATION #: Y164807
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
LIGHT IN ELEVATOR PIT FED BY LOAD SIDE OF GFI 620.24
OPEN 09/02/2014 09/02/2014
 
002 (999) OTHER
MULTIPLE COND IN ONE LUG AT CAR LIGHT,DISCONNECT SWITCH 110.14,A
OPEN 09/02/2014 09/02/2014
 
003 (999) OTHER
CONROL PANEL DISCONNECT SWITCH NOT GRD PROPERLY 250 TO GRD CONECNTRIK/O USED 250.97
OPEN 09/02/2014 09/02/2014
 
004 (999) OTHER
NO 480/277V WARNING LABEL PROVIDED FOR CONTROL PANEL DISCONNECTSWITCH AMEND.60,B
OPEN 09/02/2014 09/02/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back