Electrical Application Details for App #: Y163984
Premises: 545 EAST 172 STREET BRONX BIN: 2009658     Block: 2929   Lot: 82
   
Application Completed and Certified

Filed: 551 E 172 ST Census Tract:   167 Health Area:  2400
N/A Admin Area:   Y - BRONX Inspection Area:   D
BRONX, NY 10457 Community Board:   203
DOB Cross Street(s):    3 AVENUE,    FULTON AVENUE
Status:   C - JOB IS SIGNED OFF 08/24/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/01/2013 11:49 AM
Application Entered:   05/01/2013 Job Start Date:   05/02/2013
Last Change:   08/24/2013 Job End Date:   06/02/2013
Appointment Status:   
Last Inspection By:   SCHIAVO, JAMES       On     08/22/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012446 Licensee Name: ROOPCHAND SINGH
Firm: 003650 Firm Name: ELECTROTEC OF NY ELECL IN
Firm Phone: 212-785-0065  Firm Address: ONE (55) EXCHANGE PLZ (BROADWAY) NEW YORK NY 10006 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
9 - OTHER
Total Fee:  $44.25
Other Work:   RETROFIT EXISTING LIG
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   STORE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: N/A N/A
Owner Business Name: AMIGOS GROCERY CORP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    27                     
Buildings Total 27                        
Total Units : 27 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/22/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RETROFIT EXISTING LIGHT FIXTURE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y163984
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/12/2013 06/22/2013 JSV V (55) (4) Y
INSPECTION COMMENTS: ISSUE VIOLATION ON CONTRACTOR(JOB COMPLETE)
 
(2) 08/22/2013 08/24/2013 JSV C R (45) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: Y163984
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
1ST FLOOR-CEILING, JUNTION BOX, BLACK, WHITE AND GREEN WIRES SPLICEDTOGETHER NOT AS PER CODE. ARTICLE 250.119
RSLV 06/12/2013 06/12/2013 08/22/2013
 
002 (999) OTHER
1ST FLOOR-MC CABLE GREEN WIRES CUT OFF. NOT AS PER CODEARTICLE 250.148
RSLV 06/12/2013 06/12/2013 08/22/2013
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
1ST FLOOR- CEILING LIGHTS (FLOURESCENT), MC CABLE GREEN WIRE NOTNOT CONNECTED IN LIGHT OR J-BOX
RSLV 06/12/2013 06/12/2013 08/22/2013
 
004 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
1ST FLOOR-CEILING, LAM CORD RUN IN J BOX AS PART OF BRANCH WIRINGTHROUGH CEILING
RSLV 06/12/2013 06/12/2013 08/22/2013