BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y163729
Premises: 514 EAST 187 STREET BRONX BIN: 2011703     Block: 3055   Lot: 57
   

DOB NOW: Inspections


Filed: 514 E 187 ST Census Tract:   387
GARAGE Admin Area:   Y - BRONX Inspection Area:   I
BRONX, NY 10458 Community Board:   206
Special Place Name:   SERVICE EQUIPMENT
DOB Cross Street(s):    3 AVENUE,    BATHGATE AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   04/10/2013 Job Start Date:  
Last Change:   08/22/2025 Job End Date:  
Appointment Status:    Complaint Number:    2183657
Last Inspection By:   DORSAINVILLE, R       On     04/08/2013      
Field Disp:   W - ISSUE OBJECTION TO OWNER
Energize Recommendation:  
Objection Disposition:  

License #: Licensee Name: UNKNOWN
Firm: Firm Name: UNKNOWN
Firm Phone:   Firm Address:  

Work Started or Filed by Others: NO
Work Category:    Work To Be Done:   Total Fee:  $0.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   GARAGE
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: BENJAMIN SIGNORE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 04/10/2013
Power Issued: Response:  

Follow-Up: V - OWNER OBJECTION 04/10/2013
Contractor's Comments:  NO WATER MAIN GROUND PROVIDED

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y163729
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/08/2013 04/10/2013 RID W (15) (4)
INSPECTION COMMENTS: SEE VIOLATION DETAILS

OBJECTION FOR APPLICATION #: Y163729
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
200 AMPER SERVICE EQUIPMENTCOM: NO WATER MAIN GROUND PROVIDED
OPEN 04/08/2013 04/08/2013
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
200 AMP SERVICE SWITCHCOM: SERVICE, ENTRANCE CONDUCTOR NOT GROUNDED ON BOTH SIDE
OPEN 04/08/2013 04/08/2013
 
003 (999) OTHER
SERVICE EQUIPMENT 200 AMPER PANELCOM: MORE THAN SIX SERVICE SWITCH NO MAIN PROVIDED 230.71
OPEN 04/08/2013 04/08/2013
 
004 (999) OTHER
THIS IS NOT A FINAL INSPECTION. SEE THIS COMPLAINT #2183657
OPEN 04/08/2013 04/08/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back