BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y160770
Premises: 870 COURTLAND AVENUE BRONX BIN: 2116642     Block: 2407   Lot: 7501
   
Application Completed and Certified

Filed: 870 COURTLAND AV Census Tract:   141 Health Area:  3400
FIRST FLOOR Admin Area:   Y - BRONX Inspection Area:   C
BRONX, NY 10451 Community Board:   203
Special Place Name:   BRONX DEFENDERS
DOB Cross Street(s):   EAST 160 STREET,    EAST 161 STREET
Status:   C - JOB IS SIGNED OFF 04/11/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/17/2012 9:47 AM
Application Entered:   07/17/2012 Job Start Date:   07/18/2012
Last Change:   04/11/2013 Job End Date:   11/18/2012
Appointment Status:   
Last Inspection By:   SCHIAVO, JAMES       On     03/19/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011903 Licensee Name: WIESLAW MAKSIM
Firm: 003541 Firm Name: DENMAR ELECTRIC CORP
Firm Phone: 718-533-6753  Firm Address: 5 PENN PLAZA 19TH FLOOR NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $265.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSE MENDEZ
Owner Business Name: EXCEL INTERIOR CONSTRUCT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  2 SETS 250 KCMIL
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  42 CIRCUITS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001      41    19  70             
Buildings Total   41    19  70                
Total Units : 130 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/23/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  BRONX DEFENDERS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y160770
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/22/2013 02/23/2013 JSV A (45) (3) Y
INSPECTION COMMENTS: ISSUE VIOL TO CONTRACTOR
 
(2) 03/19/2013 04/02/2013 JSV C R (45) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: Y160770
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
1ST FL- 400 AMP PNL WITH AL FEEDERS
RSLV 01/22/2013 01/22/2013 03/19/2013
 
002 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
ALL PANELS
RSLV 01/22/2013 01/22/2013 03/19/2013
 
003 (999) OTHER
1ST FL 600 AMP SW- MULTI- LUGGING 110.14(A)
RSLV 01/22/2013 01/22/2013 03/19/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.