BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y159267
Premises: 2390 CRESTON AVENUE BRONX BIN: 2013792     Block: 3165   Lot: 11
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 2390 CRESTON AV Census Tract:   237.03 Health Area:  1600
CELLAR Admin Area:   Y - BRONX Inspection Area:   F
BRONX, NY 10468 Community Board:   205
DOB Cross Street(s):   EAST 184 STREET,    EAST 188 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/10/2012 9:57 PM
Application Entered:   03/10/2012 Job Start Date:   03/12/2012
Last Change:   08/22/2025 Job End Date:   03/12/2013
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   FATA, LUIGI       On     06/28/2016      
Field Disp:   N - NO ACCESS
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 012301 Licensee Name: AARON LEBOVITS
Firm: 004070 Firm Name: METRO ELEC'L CONTRS, INC
Firm Phone: 718-439-7466  Firm Address: 218 HAMILTON AVENUNE BROOKLYN NY 11231 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
012302 WEBER, MAYER 004070 METRO ELEC'L CONTRS, INC

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
8 - BOILER/BURNER WIRING
Total Fee:  $82.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 2390 CRESTON LLC
Authorized Representative:  R BAUE
Relationship To Owner:   REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL                     
Buildings Total                       
Total Units : 2 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: C - CALL TO OFFICE 03/24/2014
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y159267
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/23/2012 09/07/2012 JSV A (35) (4) Y
INSPECTION COMMENTS: ISSUE VIOL TO CONTRACTOR
 
(2) 12/03/2012 12/12/2012 PDI H X (30) (0) Y
INSPECTION COMMENTS: VIOL NOT REMOVED
 
(3) 03/18/2014 03/24/2014 JSV H X (40) (0) Y
INSPECTION COMMENTS: OBJECTIONS NOT REMOVED
 
(4) 06/28/2016 06/29/2016 LUF N (20) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR NO ANSWER

OBJECTION FOR APPLICATION #: Y159267
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
PHASES FOR PANEL FEED NOT IN SAME RACEWAY 300.3(B)
OPEN 08/23/2012 03/18/2014
 
002 (999) OTHER
TROUGH BELOW PANEL WITH DIFFERENT INSULATORS 300.3(C)1
OPEN 08/23/2012 03/18/2014
 
003 ( 9) SQ AREA OF SUM OF CONDUCTORS EXCEEDS SQ AREA FILL OF RACEWAY
FEED FOR BOILER , 4/6 IN 1/2 EMT
OPEN 08/23/2012 03/18/2014
 
004 ( 31) MORE THAN ALLOWABLE # OF CONDUCTORS ARE IN OUTLET BOX
J-BOX FOR BOILER DIS. OVER FILLED
OPEN 08/23/2012 03/18/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back