BIS Menu  |  Plumb. Inspections  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y158823
Premises: 499 EAST 188 STREET BRONX BIN: 2127594     Block: 3058   Lot: 41
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 499 E 188 ST Census Tract:   387 Health Area:  1000
ENTIRE BLDG Admin Area:   Y - BRONX Inspection Area:   I
BRONX, NY 10458 Community Board:   206
Related Job Number:    201066489
DOB Cross Street(s):   WASHINGTON AVENUE,    BATHGATE AVENUE
Status:   C - JOB IS SIGNED OFF 01/10/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/27/2012 2:16 PM
Application Entered:   01/27/2012 Job Start Date:   01/27/2012
Last Change:   01/10/2017 Job End Date:   01/26/2013
Appointment Status:   
Last Inspection By:   DIMAGGIO, PHILLIP       On     12/30/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011041 Licensee Name: SALVATORE CHIARAMONTE
Firm: 003893 Firm Name: L&B ELEC'L INTERNATIONAL
Firm Phone: 347-295-0380  Firm Address: 150-50 11TH AVENUE WHITESTONE NY 11357 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $1,544.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BRONX NY E 188 ST APARTMENTS LP
Owner Business Name: BRONX NY E 188 ST APTS LP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  200 A 3P, FOR HP, FP
C. 201 Up to 600 AMPS  2  400 A 3P, FOR APT'S
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  3  3 SETS 500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  40  APT PANELS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  HP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    45    10  49  10     
001    28    10      10     
002    35  85  10  10  10         
003    35  85  10  10  10         
004    35  85  10  10  10         
005    35  85  10  10  10         
006    35  85  10  10  10         
007    35  85  10  10  10         
008    35  85  10  10  10         
009    41  85  10  10  10         
ROF  BULKH    41         
ROF  LOWER                   
ROF  ROOF           
Buildings Total 365  696  80  94  104     106         
Total Units : 1447 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 41 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/27/2012 Notice: 1 - FIRST NOTICE 11/30/2016
Power Issued: 01/27/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y158823
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/09/2013 12/11/2013 PDI J E (15) (0) Y
INSPECTION COMMENTS: SPOKE TO SEAL 917-627-9903/JOE STILL IN PROGRESS
 
(2) 11/29/2016 11/30/2016 GIG V (33) (4)
INSPECTION COMMENTS: INSPECTION FAILED OBJECTION ISSUED
 
(3) 12/30/2016 12/30/2016 PDI C R (5) (0)
INSPECTION COMMENTS: PASS, REF TO APP #Y180361, CONTRACTOR SENT PHOTOS TO INSPECTOR JOFFREE PENNA ON FUSE CHANGES ETC , INSO=PECTOR OKAY WITH JOB.

OBJECTION FOR APPLICATION #: Y158823
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(BASEMENT) KOS MISSING IN FIRE PUMP SERVICE SWITCH
RSLV 11/29/2016 11/29/2016 12/30/2016
 
002 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(BASEMENT)SERVICE OVER 1000KW NEEDS ADVISORY BOARD APPROVAL NYC AMENDMENTS
RSLV 11/29/2016 11/29/2016 12/30/2016
 
003 (999) OTHER
(BASEMENT) DEFECTIVE FUSE IN DIRE PUMP SERVICE SWITCH
RSLV 11/29/2016 11/29/2016 12/30/2016
 
004 (999) OTHER
(BASEMENT) ALL MIGB NOT PROPERLY INSTALLED
RSLV 11/29/2016 11/29/2016 12/30/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back