BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y156067
Premises: 2609 AQUEDUCT AVENUE BRONX BIN: 2092426     Block: 3215   Lot: 8
   

DOB NOW: Inspections


Filed: 2609 AQUEDUCT AV Census Tract:   265 Health Area:  0320
BSMT Admin Area:   Y - BRONX Inspection Area:   F
BRONX, NY 10468 Community Board:   207
DOB Cross Street(s):   WEST 192 STREET,    RESERVOIR AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   06/06/2011 Job Start Date:  
Last Change:   08/22/2025 Job End Date:  
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     05/17/2011      
Field Disp:   W - ISSUE OBJECTION TO OWNER
Energize Recommendation:  
Objection Disposition:  

License #: Licensee Name: UNKNOWN
Firm: Firm Name: UNKNOWN
Firm Phone:   Firm Address:  

Work Started or Filed by Others: NO
Work Category:    Work To Be Done:   Total Fee:  $0.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: 2609 REALTY LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 06/06/2011
Power Issued: Response:  

Follow-Up: V - OWNER OBJECTION 06/06/2011
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y156067
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/17/2011 06/06/2011 GYM W (25) (7)
INSPECTION COMMENTS: VIOL

OBJECTION FOR APPLICATION #: Y156067
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
GRD ELECTRODE CONDUCTOR IS TERMINATED AT WATERMAIN(DEFECTIVE CLAMP)
OPEN 05/17/2011 05/17/2011
 
002 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
GRD ELECTRODE RACEWAY FROM 400A SER SW TO WATERMAIN
OPEN 05/17/2011 05/17/2011
 
003 ( 19) DEFECTIVE WIRING IS IN USE
FEED FOR EMERGENCY SHUT OFF SWITCH WIRING
OPEN 05/17/2011 05/17/2011
 
004 ( 29) OUTLET BOXES ARE NOT COVERED
BSMT PLP PANEL
OPEN 05/17/2011 05/17/2011
 
005 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
BSMT
OPEN 05/17/2011 05/17/2011
 
006 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
BSMT
OPEN 05/17/2011 05/17/2011
 
007 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
BSMT
OPEN 05/17/2011 05/17/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.