BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y154665
Premises: 689 MORRIS AVENUE BRONX BIN: 2114677     Block: 2442   Lot: 60
   
Application Completed and Certified

Filed: 675 MORRIS AV Census Tract:   65 Health Area:  3800
1FL/LAUNDROMAT Admin Area:   Y - BRONX Inspection Area:   B
BRONX, NY 10451 Community Board:   201
DOB Cross Street(s):   EAST 153 STREET,    EAST 155 STREET
Status:   C - JOB IS SIGNED OFF 02/03/2015
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   11/05/2014 Job Start Date:   11/06/2014
Last Change:   02/03/2015 Job End Date:   12/19/2014
Appointment Status:   
Last Inspection By:   SCHIAVO, JAMES       On     12/16/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011741 Licensee Name: MIKHAIL LERMAN
Firm: 003369 Firm Name: MSM ELECTRIC, INC.
Firm Phone: 718-646-5825  Firm Address: 417 BRIGHTON BEACH AVENUE.2FL BROOKLYN NY 11235 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
9 - OTHER
Total Fee:  $1,690.00
Other Work:   REMOVE VIOLATION
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   STORE, LAUNDROMATE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DORON RESHEFF
Owner Business Name: KNICKERBOCKER CONSTRACTIO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  3  3-200AMP 3 PHASE 208V
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  2  2 800AMP 3 PH 208V
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  3 SETS OF 4 #3/0
D. Over 250 MCM  2  2 SETS OF 4 500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 3 #10-Wire 2
Existing Meters 0 + New Meters 5 - Removed Meters 0 = Total Meters 5

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/05/2014 Notice:  02/15/2011
Power Issued: 11/05/2014 Response: F - FILED TO REMOVE OBJECTION 11/05/2014

Follow-Up: X - FILED APPL,NOW CLOSED 11/05/2014
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y154665
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/14/2011 02/15/2011 GYM W (10) (3)
INSPECTION COMMENTS: VIOL
 
(2) 12/16/2014 12/24/2014 JSV C R E (30) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: Y154665
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
METER PAN,800A DISC,SW,2SETS,500 MCM,2-400A MC PANEL/ LAUNDRMAT
RSLV 02/14/2011 02/14/2011 12/16/2014
 
002 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
PROVIDED CAL#,1-800A DISC SW,TAP OFF LOAD SIDE 2000A SER SWLAUNDROMAT
RSLV 02/14/2011 02/14/2011 12/16/2014
 
003 (999) OTHER
ART 240.12 PROVIDED FUSE COORDINATION,800A FUSES TO BKERS
RSLV 02/14/2011 02/14/2011 12/16/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order