| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
2 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
1 |
|
| E. Over 1200 AMPS |
1 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
84 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
8 |
|
| D. Over 250 MCM |
6 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
84 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
8 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL BSMT-PROVIDED CAL# 4000A SER SW |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 002 |
(999) |
OTHER BSMT)ART 110.26 FIRE RATED DOOR WITH PANIC,HARDWARE NOT PROVIDED FORNEW 4000A SER SW |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 003 |
(999) |
OTHER A)ART 250.28 30A SER SWS NUETRAL BAR IS NOT BONDED/BSMT |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 004 |
(999) |
OTHER B)BSMT 695.4B FIRE PUMP SER SW NOT MARKED |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 005 |
(999) |
OTHER C)ALL FLRS/ART 250.24 APS PANELS NEUTRAL BAR BONDED AFTER SS |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 006 |
(999) |
OTHER D)BSMT,ART 695.6B,RACEWAY OUTSIDE OF SER AND CONTRAL ROOM IS NOTENCLOSE IN 2INCH OF CONCRETE |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 007 |
(999) |
OTHER E)8FL, ART 210.8 NO GFCI OUTLET PROVIDED COMMUNITY ROOM |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 008 |
(999) |
OTHER F)8FL,BSMT, ART 250.30 NO GROUND PROVIDED FOR TRANSFORMER |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 009 |
(999) |
OTHER G)8FL,BSMT,ART 450.3 NO DISCONNECT SW PROVIDED FOR TRANSFORMER |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 010 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED BEDROOMS, A/L RECEPTS & LIGHTS |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 011 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) BSMT/ ELECTRICAL ROOM |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 012 |
(999) |
OTHER AC & GFCI RECEPTS IS NOT AS PER ART 250.146 |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 013 |
( 35) |
APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS BEDROOM & LIVING ROOM A/C RECE?PTS |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 014 |
( 6) |
FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION LOAD CALCULATION 1200A FUSE IN 4000A SER SW |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 015 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED CANOPY/LIGHTS REAR NOT SUITABLE FOR USED/DRY LOCATION (OUTDOOR USED |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 016 |
( 37) |
MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED REAR YARD A/C UNIT |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 017 |
( 30) |
OUTLET BOXES ARE NOT SECURED RECEPT BOXES THRU-OUT APTS |
RSLV |
06/27/2011 |
08/17/2011 |
09/23/2011 |
| |
| 018 |
(999) |
OTHER BSMT/ 8FLR NOT PROVIDED WITH VERTICAL CABLE SUPPORT 1/0 ASG WIREIS NOT AS PER ART 300.19 |
RSLV |
09/23/2011 |
09/23/2011 |
10/22/2011 |
| |
| 019 |
(999) |
OTHER A)2&8FLR/COMMUNITY ROOM BRANCH CURCUIT WIRING ART 518.4 |
RSLV |
09/23/2011 |
09/23/2011 |
10/22/2011 |
| |
| 020 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL BSMT/ NEED APPROVAL DRAWING |
RSLV |
09/23/2011 |
09/23/2011 |
10/22/2011 |
| |
| 021 |
( 6) |
FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION ALL FLRS/ LOAD CALCULATION |
RSLV |
09/23/2011 |
09/23/2011 |
10/22/2011 |
| |
| 022 |
(999) |
OTHER BMST/ ART 408.3.C NEUTRAL DISCONNECT LINK IS NOT READILY ASSCESSIBLE(AMENDMENT)4000A SER SW REV2 SEE DRAWING PER ADV BD NEUTRAL DISC |
RSLV |
10/22/2011 |
10/22/2011 |
01/09/2012 |
| |
| 023 |
(999) |
OTHER CONT: NOT LOCATED IN SER CALENDAR#50451 |
RSLV |
10/22/2011 |
10/22/2011 |
01/09/2012 |
| |
| 024 |
(999) |
OTHER 8FL/COMMUNITY ROOM COUNTER TOP ART 240.146 |
RSLV |
10/22/2011 |
10/22/2011 |
01/09/2012 |
| |
| 025 |
( 6) |
FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION ALL FLOORS/ LOAD CALCULATION NEEDED |
RSLV |
10/22/2011 |
10/22/2011 |
01/09/2012 |
| |
| 026 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL BSMT/ MARKED A,B,C & N AND COLOR CODED AS PER DRAWING |
RSLV |
10/22/2011 |
10/22/2011 |
01/09/2012 |