Premises: 1468 HOE AVENUE BRONX BIN: 2117123     Block: 2988   Lot: 4
   
Application Completed and Certified

Filed: 1468 HOE AV Census Tract:   157 Health Area:  2120
BASEMENT Admin Area:   Y - BRONX Inspection Area:   D
BRONX, NY 10460 Community Board:   203
Related Job Number:    220032355
DOB Cross Street(s):   JENNINGS STREET,    EAST 172 STREET
Status:   C - JOB IS SIGNED OFF 03/12/2012
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   08/03/2010 Job Start Date:   07/26/2010
Last Change:   03/12/2012 Job End Date:   07/26/2011
Appointment Status:   
Last Inspection By:   ASHMAN, K.       On     01/09/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012320 Licensee Name: RICHARD F FEIL
Firm: 003215 Firm Name: QUEST ELECTRIC CORP.
Firm Phone: 718-885-3367  Firm Address: 2362 WESTCHESTER AVENUE BRONX NY 10462 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: MACQUESTEN CONTRACTING
Authorized Representative:  RELIA FOGLIANO
Relationship To Owner:   X


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  
E. Over 1200 AMPS  1  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  84  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  8  
D. Over 250 MCM  6  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  84  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  8  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    50  15  15  71             
001    40  70  25  141         
002    100  120  12  50  282             
003    100  120  12  50  282             
004    100  120  12  50  282             
005    100  120  12  50  282             
006    100  120  12  50  282             
007    100  120  12  50  282             
008    70  50  25  149             
ROF    10  22             
Buildings Total 764  861  85  375  2075              
Total Units : 4161 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 84 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/03/2010 Notice: 1 - FIRST NOTICE 11/09/2011
Power Issued: 08/03/2010 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y152327
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/27/2011 07/11/2011 GYM V E (150) (17) Y
INSPECTION COMMENTS: VIOL
 
(2) 08/17/2011 08/29/2011 KAS H X G (90) (0) Y
INSPECTION COMMENTS: JOB IN PROGRESS
 
(3) 09/23/2011 10/05/2011 GYM A R E (85) (4) Y
INSPECTION COMMENTS: VIOL
 
(4) 10/22/2011 11/09/2011 GYM A R E (120) (5) Y
INSPECTION COMMENTS: VIOL
 
(5) 01/09/2012 01/26/2012 KAS C R E (60) (0) Y
INSPECTION COMMENTS: CERT

OBJECTION FOR APPLICATION #: Y152327
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
BSMT-PROVIDED CAL# 4000A SER SW
RSLV 06/27/2011 08/17/2011 09/23/2011
 
002 (999) OTHER
BSMT)ART 110.26 FIRE RATED DOOR WITH PANIC,HARDWARE NOT PROVIDED FORNEW 4000A SER SW
RSLV 06/27/2011 08/17/2011 09/23/2011
 
003 (999) OTHER
A)ART 250.28 30A SER SWS NUETRAL BAR IS NOT BONDED/BSMT
RSLV 06/27/2011 08/17/2011 09/23/2011
 
004 (999) OTHER
B)BSMT 695.4B FIRE PUMP SER SW NOT MARKED
RSLV 06/27/2011 08/17/2011 09/23/2011
 
005 (999) OTHER
C)ALL FLRS/ART 250.24 APS PANELS NEUTRAL BAR BONDED AFTER SS
RSLV 06/27/2011 08/17/2011 09/23/2011
 
006 (999) OTHER
D)BSMT,ART 695.6B,RACEWAY OUTSIDE OF SER AND CONTRAL ROOM IS NOTENCLOSE IN 2INCH OF CONCRETE
RSLV 06/27/2011 08/17/2011 09/23/2011
 
007 (999) OTHER
E)8FL, ART 210.8 NO GFCI OUTLET PROVIDED COMMUNITY ROOM
RSLV 06/27/2011 08/17/2011 09/23/2011
 
008 (999) OTHER
F)8FL,BSMT, ART 250.30 NO GROUND PROVIDED FOR TRANSFORMER
RSLV 06/27/2011 08/17/2011 09/23/2011
 
009 (999) OTHER
G)8FL,BSMT,ART 450.3 NO DISCONNECT SW PROVIDED FOR TRANSFORMER
RSLV 06/27/2011 08/17/2011 09/23/2011
 
010 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
BEDROOMS, A/L RECEPTS & LIGHTS
RSLV 06/27/2011 08/17/2011 09/23/2011
 
011 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
BSMT/ ELECTRICAL ROOM
RSLV 06/27/2011 08/17/2011 09/23/2011
 
012 (999) OTHER
AC & GFCI RECEPTS IS NOT AS PER ART 250.146
RSLV 06/27/2011 08/17/2011 09/23/2011
 
013 ( 35) APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS
BEDROOM & LIVING ROOM A/C RECE?PTS
RSLV 06/27/2011 08/17/2011 09/23/2011
 
014 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
LOAD CALCULATION 1200A FUSE IN 4000A SER SW
RSLV 06/27/2011 08/17/2011 09/23/2011
 
015 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
CANOPY/LIGHTS REAR NOT SUITABLE FOR USED/DRY LOCATION (OUTDOOR USED
RSLV 06/27/2011 08/17/2011 09/23/2011
 
016 ( 37) MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED
REAR YARD A/C UNIT
RSLV 06/27/2011 08/17/2011 09/23/2011
 
017 ( 30) OUTLET BOXES ARE NOT SECURED
RECEPT BOXES THRU-OUT APTS
RSLV 06/27/2011 08/17/2011 09/23/2011
 
018 (999) OTHER
BSMT/ 8FLR NOT PROVIDED WITH VERTICAL CABLE SUPPORT 1/0 ASG WIREIS NOT AS PER ART 300.19
RSLV 09/23/2011 09/23/2011 10/22/2011
 
019 (999) OTHER
A)2&8FLR/COMMUNITY ROOM BRANCH CURCUIT WIRING ART 518.4
RSLV 09/23/2011 09/23/2011 10/22/2011
 
020 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
BSMT/ NEED APPROVAL DRAWING
RSLV 09/23/2011 09/23/2011 10/22/2011
 
021 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
ALL FLRS/ LOAD CALCULATION
RSLV 09/23/2011 09/23/2011 10/22/2011
 
022 (999) OTHER
BMST/ ART 408.3.C NEUTRAL DISCONNECT LINK IS NOT READILY ASSCESSIBLE(AMENDMENT)4000A SER SW REV2 SEE DRAWING PER ADV BD NEUTRAL DISC
RSLV 10/22/2011 10/22/2011 01/09/2012
 
023 (999) OTHER
CONT: NOT LOCATED IN SER CALENDAR#50451
RSLV 10/22/2011 10/22/2011 01/09/2012
 
024 (999) OTHER
8FL/COMMUNITY ROOM COUNTER TOP ART 240.146
RSLV 10/22/2011 10/22/2011 01/09/2012
 
025 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
ALL FLOORS/ LOAD CALCULATION NEEDED
RSLV 10/22/2011 10/22/2011 01/09/2012
 
026 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
BSMT/ MARKED A,B,C & N AND COLOR CODED AS PER DRAWING
RSLV 10/22/2011 10/22/2011 01/09/2012