BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y151869
Premises: 1531 UNIVERSITY AVENUE BRONX BIN: 2092104     Block: 2877   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1535 UNIVERSITY AV Census Tract:   205 Health Area:  2210
FEATHERBED LANE Admin Area:   Y - BRONX Inspection Area:   E
BRONX, NY 10453 Community Board:   205
DOB Cross Street(s):   CROSS BRONX EP ET 1 D-1 C WB,    FEATHERBED LANE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/27/2010 9:33 AM
Application Entered:   06/27/2010 Job Start Date:   08/01/2010
Last Change:   11/26/2025 Job End Date:   09/30/2010
Appointment Status:   
Last Inspection By:   ASHMAN, K.       On     08/08/2011      
Field Disp:   N - NO ACCESS
Energize Recommendation:  
Objection Disposition:  

License #: 010552 Licensee Name: JOSEPH BRAMAN
Firm: 003886 Firm Name: NEE ELECTRICAL, LLC
Firm Phone: 718-349-4756  Firm Address: 47-55 37TH STREET LONG ISLAND CITY NY 11101 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
009891 WHALEN, WILLIAM T 003886 NEE ELECTRICAL, LLC

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $456.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DOMINICO VITULLI
Owner Business Name: NYCHA
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  
B. Each Additional 10 Floors Or Less  2  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 07/21/2011
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  2P2620, 2P2621

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y151869
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/14/2011 07/21/2011 GYM A (45) (3) Y
INSPECTION COMMENTS: ELEVATOR 14 FLOORS/ NYC#2P2620, 2P2621
 
(2) 08/08/2011 08/18/2011 KAS N (30) (0) Y
INSPECTION COMMENTS: NA

OBJECTION FOR APPLICATION #: Y151869
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT TO ROOF/ TABLE 300.19A,SUPPORT OF CONDUCTOR IN VERTICAL RACEWAY BSMT TO ROOF
OPEN 07/14/2011 07/14/2011
 
002 (999) OTHER
A- BSMT TO ROOR/ ART 620.37 MAIN FEEDERS SUPPLYING POWER TO THEELEVATOR SHALL BE INSTALLED OUTSIDE THE HOISTWAY
OPEN 07/14/2011 07/14/2011
 
003 (999) OTHER
B-ROOF, SUB-SECTION 210.19 BRANCH CIRCUIT WIRING ELEVATOR ROOM ISNOT #12 AWE,#14 USED
OPEN 07/14/2011 07/14/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.