BIS Menu  |  Applications  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y151865
Premises: 150 WEST 174 STREET BRONX BIN: 2092106     Block: 2877   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 150 W 174 ST Census Tract:   205 Health Area:  2210
POPHAM AVE Admin Area:   Y - BRONX Inspection Area:   E
BRONX, NY 10453 Community Board:   205
DOB Cross Street(s):   POPHAM AVENUE,    POPHAM AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/27/2010 9:14 AM
Application Entered:   06/27/2010 Job Start Date:   08/01/2010
Last Change:   11/26/2025 Job End Date:   09/30/2012
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     07/08/2011      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 010552 Licensee Name: JOSEPH BRAMAN
Firm: 003886 Firm Name: NEE ELECTRICAL, LLC
Firm Phone: 718-349-4756  Firm Address: 47-55 37TH STREET LONG ISLAND CITY NY 11101 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
009891 WHALEN, WILLIAM T 003886 NEE ELECTRICAL, LLC

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $456.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DOMINICO VITULLI
Owner Business Name: NYCHA
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  
B. Each Additional 10 Floors Or Less  2  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 07/19/2011
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  4P2612, 4P2613

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y151865
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/08/2011 07/19/2011 GYM A (50) (4) Y
INSPECTION COMMENTS: ELEVATOR 14 FLOOR ID 2P2612 2P2613

OBJECTION FOR APPLICATION #: Y151865
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT ARTICLE 620.37 FEEDER SUPPLYING POWER TO ELEVATOR SHALL BE INSTALLED OUTSIDE THE HOIST WAY FROM BSMT TO ROOF
OPEN 07/08/2011 07/08/2011
 
002 (999) OTHER
(A) BASEMENT TABLE 300.18 SUPPORT OF CONDUCTORS IN VERTIAL RACEWAY FROM BSMT TO ROOF
OPEN 07/08/2011 07/08/2011
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ROOF CONTROL PANELS DOORS
OPEN 07/08/2011 07/08/2011
 
004 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
BASEMENT TO ROOF ELEVATOR FEEDER FROM BASEMENT TO ROOF RACEWAY
OPEN 07/08/2011 07/08/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.