BIS Menu  |  DOB Violations  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y151656
Premises: 1139 NOBLE AVENUE BRONX BIN: 2092821     Block: 3749   Lot: 60
   
Application Completed and Certified

Filed: 1139 NOBLE AV Census Tract:   68 Health Area:  3010
BASEMENT Admin Area:   Y - BRONX Inspection Area:   J
BRONX, NY 10472 Community Board:   209
DOB Cross Street(s):   WATSON AVENUE,    GLEASON AVENUE
Status:   C - JOB IS SIGNED OFF 09/08/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/11/2010 8:40 AM
Application Entered:   06/11/2010 Job Start Date:   06/11/2010
Last Change:   09/08/2010 Job End Date:   06/11/2011
Appointment Status:   
Last Inspection By:   ROGALEWSKI, M       On     08/20/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  B - CANCEL POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012177 Licensee Name: EWAN PALMER
Firm: 003891 Firm Name: PRINCIPAL ELECTRICAL CORP
Firm Phone: 718-405-7609  Firm Address: 3564 BOSTON ROAD BRONX NY 10469 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $48.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: NORMA FERNANDEZ
Owner Business Name: OWNER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  COMBO PANEL
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 4 #4-Wire 0 #10-Wire 0
Existing Meters 3 + New Meters 4 - Removed Meters 3 = Total Meters 4

Power Auth Flag: K - CANCELLED Objection Flag:
Power Requested: 06/11/2010 Notice: 1 - FIRST NOTICE 07/28/2010
Power Issued: 06/11/2010 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ADD PLP METER

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Y151656
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/20/2010 07/28/2010 NEI A B (45) (5) Y
INSPECTION COMMENTS: V
 
(2) 08/20/2010 08/25/2010 MIR C R (30) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: Y151656
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
E1B/SERVICE ENTRANCE NOT BONDED-E1B LOCKNUT IS NOT MADE UP TIGHT
RSLV 07/20/2010 07/20/2010 08/20/2010
 
002 (999) OTHER
SER/SER SWI IS NOT MADE UP TIGHT..(408.36.F
RSLV 07/20/2010 07/20/2010 08/20/2010
 
003 (999) OTHER
PLP SER SWI/ NEUTRAL BAK IS NOT BONDED 250.28
RSLV 07/20/2010 07/20/2010 08/20/2010
 
004 (999) OTHER
SUPP GRD/CONDUCTOR SMALLER THAN 1/0 RAN IN PARREL 2#6 (310.4)
RSLV 07/20/2010 07/20/2010 08/20/2010
 
005 (999) OTHER
WATER MAIN/LUG IS NOR PROVIDED FOR STRANDED GRD CONDUCTOR AT WATERMAIN 250.70
RSLV 07/20/2010 07/20/2010 08/20/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.